2016-07-20 07:11:251ST REVIEW MECHANICAL
 PERMIT #16070337
 7/20/16
  
 1) M1: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF RTU-2.
  
 2) M1: & M2: REFER TO TABLE 403.3 AND PROVIDE AN
 EXHAUST VENTILATION CALCULATION FOR THE COPY ROOM, AND
 PROVIDE COMPLETE DETAILS FOR THE EXHAUST SYSTEM- SHOW
 LOCATION OF EXHAUST FAN(S), EXHAUST DUCT RUNS, AND
 PROVIDE FAN EQUIPMENT SCHEDULE(S).
  
 3) M2: AS NOTED IN THE RTU MOUNTING DETAIL, PLEASE
 PROVIDE COMPLETE STRUCTURAL DETAILS FOR ATTACHING THE
 RTU TO THE CURB AND THE CURB TO THE ROOF STRUCTURE-
 SECTION 301.15. SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE CURB ADAPTERS (REFERENCED ON M1) WITH SHOP
 DRAWING APPROVAL SIGNATURE BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER