| Notes |
| Date |
Text |
| 2016-07-20 07:11:25 | 1ST REVIEW MECHANICAL | | | PERMIT #16070337 | | | 7/20/16 | | | | | | 1) M1: PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR | | | SYSTEM OF RTU-2. | | | | | | 2) M1: & M2: REFER TO TABLE 403.3 AND PROVIDE AN | | | EXHAUST VENTILATION CALCULATION FOR THE COPY ROOM, AND | | | PROVIDE COMPLETE DETAILS FOR THE EXHAUST SYSTEM- SHOW | | | LOCATION OF EXHAUST FAN(S), EXHAUST DUCT RUNS, AND | | | PROVIDE FAN EQUIPMENT SCHEDULE(S). | | | | | | 3) M2: AS NOTED IN THE RTU MOUNTING DETAIL, PLEASE | | | PROVIDE COMPLETE STRUCTURAL DETAILS FOR ATTACHING THE | | | RTU TO THE CURB AND THE CURB TO THE ROOF STRUCTURE- | | | SECTION 301.15. SUBMIT MANUFACTURER'S SPECIFICATIONS | | | FOR THE CURB ADAPTERS (REFERENCED ON M1) WITH SHOP | | | DRAWING APPROVAL SIGNATURE BY THE EOR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|