| 2016-07-21 09:52:58 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: NORTH AMERICAN TITLE COMPANY |
| | JOB ADDRESS: 8170 OKEECHOBEE BLVD. SUITE 8 & 9 |
| | DESCRIPTION: TENNANT BUILD OUT |
| | MAST. PERMIT: 16070337 |
| | REVISION/SUB-PERMIT: |
| | |
| | 1. NEC 600.5 REQUIRED BRANCH CIRCUIT: EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. THE SIDE DOOR |
| | SHALL THEREFORE BE PROVIDED WITH A SIGN OUTLET AS WELL. |
| | 2. PER FBC-EC405.7 ELECTRICAL POWER (MANDATORY): |
| | ACCORDING TO ASHRAE STANDARD 90.1, A MINIMUM OF 50% OF |
| | ALL 15 & 20 AMP, 125 V. RECEPTACLES SHALL BE |
| | AUTOMATICALLY CONTROLLED. SEE CODE FOR DETAILS. |
| | 3. FBC.EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT |
| | ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE |
| | DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL |
| | AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH |
| | EITHER SECTION C405.2.2.3.1 OR SECTION |
| | C405.2.2.3.2.THEREFORE, LIGHTING CIRCUITS A10 & A8 |
| | SHALL BE DESIGNATED DAYLIGHT ZONES FOR INDEPENDENT |
| | CONTROL. |
| | 4. FBC-E405.5.2 INTERIOR LIGHTING POWER: THE TOTAL |
| | INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING TO THE |
| | APPLICABLE TABLES AS INDICATED IN THIS SECTION. |
| | THEREFORE, PROVIDE A LIGHT DENSITY ALLOWANCE CHART |
| | SHOWING COMPLIANCE WITH MINIMUM LIGHT ALLOWANCE |
| | REQUIREMENTS AS PRESCRIBED BY CODE. |
| | 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICE WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | 6. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS |
| | SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY |
| | DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND |
| | TYPE OF THE SOURCE OF POWER. |
| | 7. FBC-E C405.7.3 VOLTAGE DROP: FEEDERS & CUSTOMER |
| | OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | OF 2% VOLTAGE DROP. SINCE THE DISTANCE BETWEEN THE MAIN |
| | AND THE PANELS IS NOT PROVIDED, VOLTAGE DROP |
| | CALCULATIONS SHALL BE INCLUDED ON PLANS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |