2016-08-04 08:14:48BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070337
 ADD: 8170 OKEECHOBEE BLVD SUITE 8 & 9
 CONT: ATLANTIC ENGINEERING ESERVICES INC.
 TEL: 561-358-4140
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 04/2016
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE BUILDING IS
 NON-SPRINKLERED. UNDER THE HEADING EGRESS REQUIREMENTS
 SECTION D THE PLANS QUOTE THE CODE SECTION FOR 1/3 THE
 DISTANCE APART FOR EGRESSES FBC2014 1015.2.1 PLEASE
 NOTE THIS SECTION IS FOR FIRE SPRINKLERED BUILDINGS.
 PLEASE CORRECT THIS BUILDING IS NON-SPRINKLERED.
  
 2) SHEET A1.00 DETAIL 4 SHOWS THE WATER CLOSET GRAB
 BARS MEASURED CENTERLINE FROM THE FLOOR TO THE
 CENTERLINE OF THE GRAB BAR. PLEASE SEE UNDER THE 2014
 FBC-ACCESS. CODE SECTION 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
  
 3) A1.00 THE MIRROR LOCATION SHALL BE LOCATED A MAXIMUM
 OF 40 INCHES FROM THE FINISH FLOOR TO THE BOTTOM OF THE
 REFLECTING SURFACE, SEE THE 2014 FBC-ACCESS. CODE
 SECTION 603.3.
  
 4) SHEET A1.00 SIGNAGE INDICATES SIGNAGE AT A HEIGHT OF
 60 INCHES, FIGURE 703.3.2 POSITION OF BRAILLE. 703.4
 INSTALLATION HEIGHT AND LOCATION. SIGNS WITH TACTILE
 CHARACTERS SHALL COMPLY WITH 703.4.
  
 ACCESS. CODE 703.4.1 HEIGHT ABOVE FINISH FLOOR OR
 GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48
 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 5) SHEET A2.00 SHOWS A BREAK ROOM WITH DETAILS FOUND ON
 A8.02 DETAIL # 6. PLEASE SEE THE SHEET A2.00 THE PLANS
 INDICATE THE USE OF A MICROWAVE OVEN, THE MICROWAVE
 OVEN IS NOT SHOWN IN THE DETAILS FOUND ON A8.02. PLEASE
 PROVIDE COMPLIANCE WITH:
 2014 ACCESS CODE REACH RANGES 308.1. & 309.2, 309.3 &
 309.4.
  
 6) SHEET M2 INDICATES A NEW ROOFTOP RTU, ATTACHING TO
 AN EXISTING CURB. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR THE CURB ADAPTOR, ANCHORING OF THE
 CURB ADAPTOR TO THE CURB AND THE RTU TO THE CURB
 ADAPTOR. 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  