| Plan Review Notes For Permit 16070314 |
| Permit Number |
16070314 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-08 17:42:32 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16070314 | | | 9/8/16 | | | | | | 1) SHEET M1.1: GENERAL NOTE #1, AND KEY NOTE #1 DO NOT | | | APPEAR TO BE APPLICABLE TO THE REVISED PLANS- PLEASE | | | REMOVE OR CLARIFY THE NOTES. | | | | | | 2) KEY NOTE #5 IS INCORRECTLY LOCATED AT A RETURN GRILL | | | IN THE CONFERENCE ROOM WALL. | | | | | | 3) THE AC CLOSET DOOR #E-13 MUST BE NON-COMBUSTIBLE- | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|