| 2016-07-13 17:18:07 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | ELECTRICAL REVIEW APPROVED WITH THE FOLLOWING |
| | EXCEPTIONS:. |
| | 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED. |
| | NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. |
| | 2. PER FBC-B 714.3.2 EXCEPTIONS: 1.1 UNLESS YOU HAVE |
| | SOLID NONCOMMUNICATING PARTITIONS, ALL ELECTRICAL BOXES |
| | IN 2 HR. RATED WALLS SHALL BE PROTECTED WITH LISTED |
| | FIRE STOPPING MATERIAL. |
| | 3. PER FBC-EC405.7, A MINIMUM OF 50% OF ALL 125V, 15 & |
| | 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED |
| | WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER |
| | CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |