| Plan Review Notes For Permit 16070309 |
| Permit Number |
16070309 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-12 18:58:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IN ORDER TO TAKE THE CEILING FAN CREDIT, THE FAN | | | BLADE DIAMETERS SHALL BE SPECIFIED ON THE PLANS TO SHOW | | | COMPLIANCE WITH FBC ENERGY CONSERVATION SECTION | | | R405.7.6. THE 42" DIAMETER CEILING FANS THAT ARE | | | SPECIFIED ON THE PLANS ARE TOO SMALL FOR THE SIZE OF | | | THE ROOMS TO CLAIM THE CEILING FAN CREDIT OPTION. SEE | | | FBC ENERGY CONSERVATION FAN SIZING TABLE R405.7.6 | | | | | | 2) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | | COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|