| 2016-07-19 16:21:18 | 7/19/16- FAILED | | | | | | SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL | | | | | | FAILED | | | | | | 1. BUILDING, MECHANICAL EQUIPMENT AND ROOF SETBACKS | | | NEED TO BE SHOWN IN A SITE PLAN OR SURVEY. | | | 2. ROOF CANNOT PROJECT MORE THAN 3FT. INTO A SETBACK. | | | 3. MECHANICAL EQUIPMENT CANNOT PROJECT MORE THAN 4FT. | | | INTO A SETBACK. | | | | | | SETBACKS | | | 1. SIDE- 5FT. MINIMUM 15FT TOTAL. | | | 2. REAR- 15FT | | | 3. FRONT-25FT. | | | | | | PASSED | | | 1. NO TREES BEING REMOVED SO NO TREE ALTERATION PERMIT | | | REQUIRED. | | | 2. BUILDING HEIGHT IS 27FT. MEETS 30FT. MAXIMUM. | | | 3. ONE UNIT NO EXTRA KITCHEN BEING ADDED WITH THE | | | ADDITION. | | | | | | PLEASE CONTACT: | | | NATHAN WIRA | | | (561)822-1442 | | | [email protected] | | | |
|