| 2016-07-19 10:27:32 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: HOLMES RESIDENCE ADDITION |
| | JOB ADDRESS: 3209 WASHINGTON RD. |
| | DESCRIPTION: RENOVATION & ADDITION TO EXISTING |
| | RESIDENCE |
| | MAST. PERMIT: 1670309 |
| | REVISION: N/A |
| | |
| | 1. ELECTRICAL NOTES ON SHEET E1 MENTION THE RELOCATION |
| | OF THE ELECTRIC METER. CORRECT OR REMOVE THIS NOTE. |
| | OTHERWISE REVISE THE SCOPE OF WORK TO INCLUDE SAME. IN |
| | SUCH A CASE, A SITE PLAN REFLECTING THE PROPOSED |
| | LOCATION OF THE NEW SERVICE & METER SHALL BE PROVIDED |
| | IN ADDITION TO A RISER DIAGRAM AS REQUIRED BY NEC 215.5 |
| | 2. FBC-RE3901.2.1 NEC 210.52 (A)(1) SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS |
| | INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. THIS |
| | IS APPLICABLE IN THE GUEST BEDROOM, BEDROOM 2 AND THE |
| | SITTING AREA OF THE SECOND FLOOR. |
| | 3. FBC-R4001.15 NEC 404.2(C). WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. THIS APPLIES TO ALL OF THE NEW |
| | ELECTRICAL WORK AND AS INSTRUCTED BY FBC-EX. FOR |
| | ALTERATIONS LEVEL 2. |
| | 4. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 5. FBC-ER3903.3 NEC 210.70(2)(C) WHERE ONE OR MORE |
| | LIGHTING OUTLET(S) ARE INSTALLED FOR INTERIOR |
| | STAIRWAYS, THERE SHALL BE A WALL SWITCH AT EACH FLOOR |
| | LEVEL, AND LANDING LEVEL THAT INCLUDES AN ENTRYWAY, TO |
| | CONTROL THE LIGHTING OUTLET(S) WHERE THE STAIRWAY |
| | BETWEEN FLOOR LEVELS HAS SIX RISERS OR MORE. THIS |
| | APPLIES TO ALL STAIRWAYS, IN THIS CASE THE SPIRAL |
| | STAIRWAY. |
| | 6. FBC-RE3902.12 NEC 210.12B - OUTLETS TO BE AFCI |
| | PROTECTED. APPLIES TO ALL NEWLY INSTALLED ELECTRICAL |
| | WIRING. |
| | 7. FBC-R4001.15 NEC 404.2(C). WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. APPLIES TO ALL NEWLY INSTALLED |
| | ELECTRICAL WIRING. |
| | 8. FBC-R315 REQUIRES THAT YOU INSTALL CO (CARBON |
| | MONOXIDE DETECTORS) AS REQUIRED BY CODE. |
| | 9. FBC-R314.3 REQUIRES THAT YOU INSTALLED SMOKE |
| | DETECTORS THROUGHOUT THE ENTIRE RESIDENCE AS IF THIS |
| | WERE NEW CONSTRUCTION IF YOU HAVE NOT ALREADY DONE SO. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |