2016-07-19 10:27:32ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: HOLMES RESIDENCE ADDITION
 JOB ADDRESS: 3209 WASHINGTON RD.
 DESCRIPTION: RENOVATION & ADDITION TO EXISTING
 RESIDENCE
 MAST. PERMIT: 1670309
 REVISION: N/A
  
 1. ELECTRICAL NOTES ON SHEET E1 MENTION THE RELOCATION
 OF THE ELECTRIC METER. CORRECT OR REMOVE THIS NOTE.
 OTHERWISE REVISE THE SCOPE OF WORK TO INCLUDE SAME. IN
 SUCH A CASE, A SITE PLAN REFLECTING THE PROPOSED
 LOCATION OF THE NEW SERVICE & METER SHALL BE PROVIDED
 IN ADDITION TO A RISER DIAGRAM AS REQUIRED BY NEC 215.5
 2. FBC-RE3901.2.1 NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. THIS
 IS APPLICABLE IN THE GUEST BEDROOM, BEDROOM 2 AND THE
 SITTING AREA OF THE SECOND FLOOR.
 3. FBC-R4001.15 NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH. THIS APPLIES TO ALL OF THE NEW
 ELECTRICAL WORK AND AS INSTRUCTED BY FBC-EX. FOR
 ALTERATIONS LEVEL 2.
 4. FBC-RE3905.8 NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 5. FBC-ER3903.3 NEC 210.70(2)(C) WHERE ONE OR MORE
 LIGHTING OUTLET(S) ARE INSTALLED FOR INTERIOR
 STAIRWAYS, THERE SHALL BE A WALL SWITCH AT EACH FLOOR
 LEVEL, AND LANDING LEVEL THAT INCLUDES AN ENTRYWAY, TO
 CONTROL THE LIGHTING OUTLET(S) WHERE THE STAIRWAY
 BETWEEN FLOOR LEVELS HAS SIX RISERS OR MORE. THIS
 APPLIES TO ALL STAIRWAYS, IN THIS CASE THE SPIRAL
 STAIRWAY.
 6. FBC-RE3902.12 NEC 210.12B - OUTLETS TO BE AFCI
 PROTECTED. APPLIES TO ALL NEWLY INSTALLED ELECTRICAL
 WIRING.
 7. FBC-R4001.15 NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH. APPLIES TO ALL NEWLY INSTALLED
 ELECTRICAL WIRING.
 8. FBC-R315 REQUIRES THAT YOU INSTALL CO (CARBON
 MONOXIDE DETECTORS) AS REQUIRED BY CODE.
 9. FBC-R314.3 REQUIRES THAT YOU INSTALLED SMOKE
 DETECTORS THROUGHOUT THE ENTIRE RESIDENCE AS IF THIS
 WERE NEW CONSTRUCTION IF YOU HAVE NOT ALREADY DONE SO.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  