2016-07-15 13:19:34APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT
 BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION
 FAMILY, NEC 2011.
 2. LABEL ALL GARAGE RECEPTACLES GFCI PROTECTED. NEC
 210.8A FBC E3902.2
 3. ADDRESS HISTORIC COMMENTS, SHOW WHERE DOOR IS
 LOCATED, EGRESS WILL REQUIRE A SWITCH AND LIGHT TO
 EXTERIOR. FBC E3903.3
 4. PROVIDE GENERAL NOTES TO INDICATE REQUIRED TAMPER
 RESISTANT RECEPTACLES. FBC RES E4002.14
 5. CLARIFY IF THERE ARE EXISTING SMOKES DETECTORS,
 COMPLY WITH FBC RES 314,315
 6. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  