| 2016-07-15 13:19:34 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE UPDATE ALL REFERENCES TO REFLECT CURRENT | | | BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION | | | FAMILY, NEC 2011. | | | 2. LABEL ALL GARAGE RECEPTACLES GFCI PROTECTED. NEC | | | 210.8A FBC E3902.2 | | | 3. ADDRESS HISTORIC COMMENTS, SHOW WHERE DOOR IS | | | LOCATED, EGRESS WILL REQUIRE A SWITCH AND LIGHT TO | | | EXTERIOR. FBC E3903.3 | | | 4. PROVIDE GENERAL NOTES TO INDICATE REQUIRED TAMPER | | | RESISTANT RECEPTACLES. FBC RES E4002.14 | | | 5. CLARIFY IF THERE ARE EXISTING SMOKES DETECTORS, | | | COMPLY WITH FBC RES 314,315 | | | 6. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL | | | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|