| 2016-07-19 11:41:18 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: INTERIOR RENOVATION W/WINDOW & DOOR |
| | REPLACEMENT |
| | JOB ADDRESS: 729 PENN ST. |
| | DESCRIPTION: MOVE INTERIOR WALLS; ADD ? BATH; NEW |
| | KITCHEN CABINETS, INSULATION, FLOOR & WALL COVERING. |
| | MAST. PERMIT: 16070290 |
| | REVISION: N/A |
| | |
| | 1. YOUR NOTES REFER TO A NON-EXISTENT EDITION OF THE |
| | NEC; THE APPLICABLE NEC EDITION IS THE 2011. |
| | 2. FBC-ER3609.3/NEC 250.94 BONDING FOR OTHER SYSTEMS. |
| | THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| | INSTALLED. |
| | 3. FBC-RE3901.7/NEC 210.52(E)(1) REQUIRES THAT THERE BE |
| | A GFCI PROTECTED OUTLET IN THE FRONT AND REAR OF EVERY |
| | DWELLING UNIT WITH GRADE LEVEL ACCESS. |
| | 4. FBC-RE3901.7/NEC 210.52(E)(3) BALCONIES. BALCONIES, |
| | DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE THE |
| | DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | INSTALLED WITHIN THE PERIMETER OF THE BALCONY, DECK, OR |
| | PORCH. THE RECEPTACLE SHALL NOT BE LOCATED MORE THAN |
| | 2.0 M (61?2 FT.) ABOVE THE BALCONY, DECK, OR PORCH |
| | SURFACE. |
| | 5. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES |
| | CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED |
| | BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR |
| | FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED |
| | AT THE SWITCH. THIS APPLIES TO ALL OF THE NEW |
| | ELECTRICAL WORK AND AS INSTRUCTED BY FBC-EX. FOR |
| | ALTERATIONS LEVEL 2. |
| | 6. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED |
| | FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY |
| | THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND |
| | INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED |
| | TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS. |
| | 7. FBC-RE3903.4/NEC 210.70(A)(3) STORAGE OR EQUIPMENT |
| | SPACES. AT LEAST ONE LIGHTING OUTLET CONTAINING A |
| | SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| | INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| | CONTAIN EQUIPMENT REQUIRING SERVICING. THE LIGHTING |
| | OUTLET SHALL BE PROVIDED AT OR NEAR THE EQUIPMENT |
| | REQUIRING SERVICING. UNLESS THE EQUIPMENT INSIDE THE |
| | ATTIC IS WITHIN 6 FT. FROM THE ENTRANCE, A PULL CHAIN |
| | FIXTURE WILL NOT COMPLY. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |