2016-12-05 17:24:592ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] SERVICE CONDUCTORS UNDERSIZED 3/0 WIRE IS REQUIRED
 FOR 200 AMPS, PROVIDE COMPLETE LOAD CALCULATION ,
 INCLUDE NEW 100 AMP PANEL SCHEDULE. FBC-107.3.5.3
  
 2] THE METER BEING USED AS A J-BOX MUST NOT EXCEED 75%
 OF THE CROSS SECTIONAL AREA INCLUDING TAPS & SPLICES. A
 WARNING LABEL MUST BE APPLIED IDENTIFYING THE CLOSEST
 DISCONNECTING MEANS FOR THE FEED THROUGH CONDUCTORS.
 NEC 312.8 ADD A BLOCK NOTE.
  
 3] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4)