| Plan Review Notes For Permit 16070282 |
| Permit Number |
16070282 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-05 17:24:59 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] SERVICE CONDUCTORS UNDERSIZED 3/0 WIRE IS REQUIRED | | | FOR 200 AMPS, PROVIDE COMPLETE LOAD CALCULATION , | | | INCLUDE NEW 100 AMP PANEL SCHEDULE. FBC-107.3.5.3 | | | | | | 2] THE METER BEING USED AS A J-BOX MUST NOT EXCEED 75% | | | OF THE CROSS SECTIONAL AREA INCLUDING TAPS & SPLICES. A | | | WARNING LABEL MUST BE APPLIED IDENTIFYING THE CLOSEST | | | DISCONNECTING MEANS FOR THE FEED THROUGH CONDUCTORS. | | | NEC 312.8 ADD A BLOCK NOTE. | | | | | | 3] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING | | | CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4) |
|