2016-07-11 14:23:11JOB PERMIT NUMBER: MASTER 15071032, REVISION 16070282
 JOB ADDRESS: 2015 PARKER AVE
 WEST PALM BEACH FLORIDA
 DATE: JULY 11 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PROVIDE LOAD CALCS AND A RISER DIAGRAM SHOWING PROPER
 SERVICE FEEDER CONDUCTOR SIZES REFERENCE NEC TABLE
 310.(B)(16)
 - WHEN MORE THAN 3 CURRENT CARRYING CONDUCTORS ARE
 INSTALLED IN A RACEWAY ADJUSTMENT FACTORS MUST BE TAKEN
 INTO CONSIDERATION, REFERENCE NEC TABLE 310.15(B)(3)(A)
 - THE EXISTING PANEL BEING USED AS A J-BOX MUST HAVE A
 WARNING LABEL THAT IDENTIFIES THE CLOSEST DISCONNECTING
 MEANS FOR ANY FEED THROUGH CONDUCTORS. NEC 312.8(3)
 - GFCI PROTECTION REQUIRED FOR ALL COMMERCIAL KITCHENS
 NEC 210.8(B)
 - INSTALL AN INTERSYSTEM BONDING TERMINAL AT THE
 SERVICE GROUNDING ELECTRODE SYSTEM. NEC 250.94
 - COMPLY WITH MANDATORY LIGHTING CONTROLS FOR NEW
 LIGHTING PER FBC-E C405
 - RECESSED LIGHTING MUST BE IC RATED AND SEALED TO
 LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND UN
 CONDITIONED SPACES. FBC-E C402.4.8
 - MEANS OF EGRESS ILLUMINATION REQUIRED, EMERGENCY &
 EXIT LIGHTS. FBC 1006.1, 1006.2, 1011.
 - REFLECT A NEW BUILDING PLAN AND FURTHER COMMENTS MAY
 BE ASKED FOR MINIMUM PLAN REVIEW. FBC 107
 - STEPHEN GAYDOSH, PE IS THE ELECTRICAL DESIGNER OF
 RECORD. ANY CHANGE TO HIS DESIGN MUST COME FROM HIM OR
 OTHERWISE DEMONSTRATE HIS APPROVAL NOT ACCEPTABLE PER
 FAC 61G15-23.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T
 HESITATE TO CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011