| 2016-07-11 14:23:11 | JOB PERMIT NUMBER: MASTER 15071032, REVISION 16070282 |
| | JOB ADDRESS: 2015 PARKER AVE |
| | WEST PALM BEACH FLORIDA |
| | DATE: JULY 11 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - PROVIDE LOAD CALCS AND A RISER DIAGRAM SHOWING PROPER |
| | SERVICE FEEDER CONDUCTOR SIZES REFERENCE NEC TABLE |
| | 310.(B)(16) |
| | - WHEN MORE THAN 3 CURRENT CARRYING CONDUCTORS ARE |
| | INSTALLED IN A RACEWAY ADJUSTMENT FACTORS MUST BE TAKEN |
| | INTO CONSIDERATION, REFERENCE NEC TABLE 310.15(B)(3)(A) |
| | - THE EXISTING PANEL BEING USED AS A J-BOX MUST HAVE A |
| | WARNING LABEL THAT IDENTIFIES THE CLOSEST DISCONNECTING |
| | MEANS FOR ANY FEED THROUGH CONDUCTORS. NEC 312.8(3) |
| | - GFCI PROTECTION REQUIRED FOR ALL COMMERCIAL KITCHENS |
| | NEC 210.8(B) |
| | - INSTALL AN INTERSYSTEM BONDING TERMINAL AT THE |
| | SERVICE GROUNDING ELECTRODE SYSTEM. NEC 250.94 |
| | - COMPLY WITH MANDATORY LIGHTING CONTROLS FOR NEW |
| | LIGHTING PER FBC-E C405 |
| | - RECESSED LIGHTING MUST BE IC RATED AND SEALED TO |
| | LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND UN |
| | CONDITIONED SPACES. FBC-E C402.4.8 |
| | - MEANS OF EGRESS ILLUMINATION REQUIRED, EMERGENCY & |
| | EXIT LIGHTS. FBC 1006.1, 1006.2, 1011. |
| | - REFLECT A NEW BUILDING PLAN AND FURTHER COMMENTS MAY |
| | BE ASKED FOR MINIMUM PLAN REVIEW. FBC 107 |
| | - STEPHEN GAYDOSH, PE IS THE ELECTRICAL DESIGNER OF |
| | RECORD. ANY CHANGE TO HIS DESIGN MUST COME FROM HIM OR |
| | OTHERWISE DEMONSTRATE HIS APPROVAL NOT ACCEPTABLE PER |
| | FAC 61G15-23. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED.IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T |
| | HESITATE TO CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |