| 2016-08-04 12:21:59 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070269 |
| | ADD: 2427 PRESIDENTIAL WAY SUITE # 301 |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: 561-427-5664 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 18/2016 |
| | ACTION: DENIED |
| | |
| | NOTICE TO CONTRACTOR, REMOVE OLD SHEETS AND INSERT NEW |
| | SHEETS< SEE COMMENT # 3!!!!!!! |
| | |
| | |
| | |
| | 1) 2ND REQUEST. THE DEMOLITION PLAN INDICATES THE |
| | REMOVAL OF ALL FLOOR FINISHES THROUGH OUT THE UNIT. |
| | SHEET A.02 MAKES REFERENCE TWICE TO THE REQUIRED FLOOR |
| | SOUND INSULATION REQUIREMENTS. THE SHEET A.02 INTERIOR |
| | NOTE # 6 INDICATES THE FLOOR FINISHES ARE TO BE |
| | SPECIFIED BY THE OWNER. THE PLANS DO NOT STATE WHICH |
| | ROOMS WILL RECIEVE WHAT FLOOR FINISHES!!!!!! WE NEED TO |
| | KNOW THAT TO BE ABLE TO MATCH UP THE TYPEOF MATERIAL TO |
| | BE INSTALLED TO THE SUBMITTED REPORT. |
| | |
| | THE PLANS REFER BACK TO THE REQUIRED TESTING REPORTS. I |
| | SPOKE LAST WEEK WITH A DESIGNER ON THIS PROJECT. DO NOT |
| | SEND IN SPEC SHEETS, WE NEED THE ACTUAL TEST. SUBMITTED |
| | IS PROFLEX MSC 90, THIS DOES NOT MEET THE REQUIREMENT |
| | WHEN YOU ACTUALLY SEE THE DOCUMENTED TEST. NEITHER DID |
| | THE DESIGNER NOR CONTRACTOR SUBMIT THE FLAME SPREAD |
| | TEST REPORT REQUESTED BELOW. |
| | CURRENTLY THE ONLY PRODUCT THAT HAS MET ALL OF THE |
| | REQUIREMENTS FOR TILE ON A 6 INCH SLAB IS THE PRODUCT |
| | PROFLEX RCU-500 WHICH IS 1/2 INCH THICK. STC 53 & IIC |
| | 50, 6 INCH CONCRETE SLAB/ NO DROPPED CEILING. |
| | |
| | |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-B. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 1A)2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) 2ND REQUEST!!!!! WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |