| 2016-07-18 11:52:30 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070269 |
| | ADD: 2427 PRESIDENTIAL WAY SUITE # 301 |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: 561-427-5664 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 18/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE DEMOLITION PLAN INDICATES THE REMOVAL OF ALL |
| | FLOOR FINISHES THROUGH OUT THE UNIT. PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2014 FBC-B. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2A) SHEET A.02 SHOWS A LIVING ROOM CEILING HEIGHT OF 8 |
| | FT. 1 IN. AND A BREAKFAST AREA WITH THE SAME FINISH |
| | CEILING AT 8 FT. 1 INCH. PLEASE NOTE THERE IS A NOTE OF |
| | A NEW 7 INCH DEEP SOFFIT ( DROPPED CEILING OVER THE |
| | KITCHEN AREA) BUT THERE IS NO INFORMATION AS TO WHERE |
| | IT ENDS? THIS ALSO HOLDS TRU WITH THE NEW MASTER BATH |
| | LAYOUT AND MASTER BATH ENTRY HALLWAY. PLEASE NOTE WITH |
| | ONLY A 7 INCH DROPPED CEILING WHERE WILL THE A/C DUCTS |
| | BE RUN SINCE THE FRAMING MEMBERS WILL TAKE |
| | APPROXIMATELY 3 1/2 INCHES OF THIS SPACE? 107.2.1.3 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 2B) THERE IS ALSO NO FRAMING INFORMATIONFOR THE DROPPED |
| | SOFFIT/ CEILING, AS TO MATERIAL, SIZE OF, GAUGE, |
| | SPACING, ANCHORING TO THE CONCRETE DECK ABOVE, TYPE OF |
| | ANCHOR, FREQUENCY OF ATTACHMENT TO THE CONRETE DECK,IF |
| | STIFF BACKS ARE REQUIRED NOR THE TYPE OF FINISH |
| | MATERIAL TO BE USED FOR THE SOFFIT/ KITCHEN CEILING NOR |
| | THE ALLOWABLE CEILING SPANS AND DEFLECTION LIMITATIONS. |
| | 2014 FBC-B TABLE 2507.2 STEEL STUDS NON-LOAD BEARING |
| | ASTM C645. ASTM C754. TABLE 1604.3 DEFLECTION. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |