| Plan Review Notes For Permit 16070262 |
| Permit Number |
16070262 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-02 13:33:37 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16070262 | | | 8/2/16 | | | | | | 1) PROVIDE CLEAR, LEGIBLE PLANS AT A MINIMUM 1/8" | | | SCALE- SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 3) PROVIDE MECHANICAL PLANS THAT CLEARLY INDICATE ATHE | | | SCOPE OF WORK WITH CORRESPONDING DRAWINGS AND DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|