2016-10-29 14:22:303RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
  
 2.3RD REQUEST PROVIDE SIZING CALCULATIONS FOR GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 3. 2ND REQUEST PREVIOUS COMMENT #11 THE ORIGINAL NOTE
 FOR THE SAMPLING PORT DOES NOT COMPLY PLEASE REVISE TO
 INCLUDE A 6" OPENING AND NO CAP OR SUMP AT THE BOTTOM
 OF THE SAMPLING PORT ,OR JUST REMOVE NOTE. PER WPB
 AMEND TO FBC 107.2.1
  
 4. SHT. P-3 WHAT STANDARD OR CODE IS THE TABLE LABELED
 GREASE FIXTURE DRAINAGE SIZING CALCULATIONS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE NOTE ON PLAN THAT A SEPARATE PERMIT
 IS REQUIRED FOR BACKFLOW DEVISE, GREASE INTERCEPTOR AND
 GAS. PER WPB AMEND TO FBC 107.2.1
  