| Plan Review Notes For Permit 16070258 |
| Permit Number |
16070258 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-10-29 14:22:30 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | | | | | | | 2.3RD REQUEST PROVIDE SIZING CALCULATIONS FOR GREASE | | | INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. 2ND REQUEST PREVIOUS COMMENT #11 THE ORIGINAL NOTE | | | FOR THE SAMPLING PORT DOES NOT COMPLY PLEASE REVISE TO | | | INCLUDE A 6" OPENING AND NO CAP OR SUMP AT THE BOTTOM | | | OF THE SAMPLING PORT ,OR JUST REMOVE NOTE. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 4. SHT. P-3 WHAT STANDARD OR CODE IS THE TABLE LABELED | | | GREASE FIXTURE DRAINAGE SIZING CALCULATIONS PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. PLEASE PROVIDE NOTE ON PLAN THAT A SEPARATE PERMIT | | | IS REQUIRED FOR BACKFLOW DEVISE, GREASE INTERCEPTOR AND | | | GAS. PER WPB AMEND TO FBC 107.2.1 | | | |
|