| 2016-07-14 15:19:30 | 1817 SOUTH DIXIE HIGHWAY |
| | PERMIT #16070258 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NO PORTABLE FIRE EXTINGUISHERS PROVIDED IN INTERIOR OR |
| | EXTERIOR SEATING AREAS. |
| | |
| | THE PLANS INDICATE AN OCCUPANT LOAD OF 104 PERSONS IN |
| | THE SEATING AREAS USING AN OCCUPANT LOAD FACTOR OF 15 |
| | SQ.FT. PER PERSON; HOWEVER, THE ACTUAL SEATING AREAS |
| | APPEAR TO BE CLOSER TO 2,300 SQUARE FEET WITH AN |
| | OCCUPANT LOAD CLOSER TO 150 OCCUPANTS. |
| | |
| | THE MAIN ENTRANCE DOOR AND THE EXTERIOR GATES SWING |
| | AGAINST EGRESS. FOR ASSEMBLY OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS/GATES TO RELEASE THE LOCK/LATCH. NO |
| | OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1-INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | THE OCCUPANT LOAD EXCEEDS 50 PERSONS FOR THE EXTERIOR |
| | SEATING AREA AND REQUIRES A SECONDARY EXIT WITH A DOOR |
| | SWINGING IN THE DIRECTION OF EGRESS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET E-2: NO ILLUMINATED EXIT SIGNS OR EMERGENCY |
| | LIGHTING PROVIDED FOR EXTERIOR SEATING AREA. |
| | |
| | SHEET E-2: EXIT SIGN IN SEATING AREA #101 CANNOT BE |
| | SEEN BY OTHER OCCUPANTS SEATING IN OTHER AREAS OF THE |
| | RESTAURANT DUE TO THE WALL OBSTRUCTING THE VIEW. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |