| Date |
Text |
| 2016-07-12 09:07:32 | 7/12/16 I SPOKE WITH THE ENGINEER TO DISCUSS THE ITEMS |
| | MENTIONED BELOW. HE UNDERSTANDS AND CONCURS WITH THE |
| | COMMENTS. WITH REGARDS TO THE SIGN OUTLET, THE REAR |
| | DOORS ARE NOT ENTRY BUT LEAD IN TO A CLOSED PATIO AREA. |
| | HE WILL INDICATE THAT ON THE DRAWINGS. IF THAT IS THE |
| | CASE THE SIGN REQUIREMENT WILL NOT APPLY AS THEY ARE |
| | NOT ENTRY DOORS. |
| | |
| | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| | DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| | CONSIDERED ACCESSIBLE TO PEDESTRIANS. THIS OUTLET IS |
| | MISSING AT THE REAR DOORS. |
| | 2. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL MEANS THAT |
| | DAYLIGHT ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN |
| | THE DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF |
| | GENERAL AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE |
| | WITH EITHER SECTION C405.2.2.3.1 OR SECTION |
| | C405.2.2.3.2. |
| | 3. NEC 110.26 HAS SPECIFIC SAFE WORKING CLEARANCE |
| | REQUIREMENTS ABOUT ELECTRICAL EQUIPMENT. |
| | 4. NEC 110.26(B) REQUIRES THAT THE DEDICATED SPACE |
| | ABOUT ELECTRICAL EQUIPMENT BE SUITABLY GUARDED. |
| | THEREFORE, BECAUSE THE ELECTRICAL PANELS WILL BE IN THE |
| | STORAGE AREA, MARK ON THE FLOOR THE REQUIRED CLEAR |
| | SPACE ABOUT THE ELECTRICAL PANELS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |