| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | RELIABLE SPRINKLER MODEL G5 WAS SUBMITTED BUT CANNOT BE |
| | LOCATED ON ANY OF THE PLANS. |
| | |
| | SITE PLAN INDICATES THE FIRE PUMP IS "NOT IN CONTRACT" |
| | HOWEVER, FIRE PUMP ISOMETRIC AND PUMP BILL OF MATERIALS |
| | HAVE BEEN PROVIDED. |
| | |
| | SUBMIT PRODUCT DATA FOR FIRE PUMP, JOCKEY PUMP, |
| | CONTROLLERS, PRESSURE REDUCING VALVES, PIPE, FITTINGS, |
| | ETC. |
| | |
| | 1ST FLOOR PLANS ARE NOT SCALABLE; HOWEVER, PLANS |
| | INDICATE A SCALE OF 3/32"=1'-0". PLANS ARE REQUIRED TO |
| | A MINIMUM OF 1/8"=1'-0". |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) |
| | INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR |
| | UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM |
| | SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF |
| | DECK (IF OBSTRUCTED CONSTRUCTION). |
| | |
| | PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM |
| | NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS |
| | PERMITTED IN THE LISTING DATA. |
| | |
| | INDICATE THE FLOORS TO BE TESTED IN EXCESS OF THE 200 |
| | PSI HYDROSTATIC TEST PRESSURE. INDICATE THE TEST |
| | PRESSURE (ABOVE 200 PSI) NEEDED AT THESE FLOORS. |
| | |
| | RELIABLE MODEL RESIDENTIAL SPRINKLERS ARE LOCATED IN |
| | SEVERAL ROOMS THAT ARE NOT DWELLING UNITS. PER NFPA 13 |
| | SECTION 8.4.5.1 RESIDENTIAL SPRINKLERS SHALL BE |
| | PERMITTED IN DWELLING UNITS AND THEIR ADJOINING |
| | CORRIDORS. |
| | |
| | SPRINKLER FLOOR CONTROL VALVES (SEVERAL SHEETS): PER |
| | NFPA 13 SECTION 8.16.1.2.2 PRESSURE GAUGES SHALL BE |
| | INSTALLED ON THE INLET AND OUTLET SIDES OF EACH |
| | PRESSURE-REDUCING VALVE. A RELIEF VALVE OF NOT LESS |
| | THAN 1/2-INCH IN SIZE SHALL BE PROVIDED ON THE |
| | DISCHARGE SIDE OF THE PRESSURE-REDUCING VALVE SET TO |
| | OPERATE AT A PRESSURE NOT EXCEEDING 175 PSI. |
| | |
| | 2ND FLOOR: SPRINKLERS LOCATED IN THE HIGH CEILING OF |
| | LIVING/LIBRARY ROOM #121 NEED TO BE SUPPLIED FROM THE |
| | 1ST FLOOR SPRINKLER SYSTEM SEEING THAT THE SPRINKLERS |
| | ARE PROTECTING THE FLOOR AREA OF THE 1ST FLOOR, |
| | OTHERWISE FIREFIGHTERS MAY INCORRECTLY ASSUME THE FIRE |
| | IS LOCATED ON THE 2ND FLOOR WHEN THE FLOW SWITCH |
| | OPERATES. |
| | |
| | 10TH FLOOR: THE HYDRAULIC CALCULATION NODES DO NOT |
| | MATCH THE HYDRAULIC NODES ON THE PLANS. FOR EXAMPLE, |
| | HYDRAULIC CALCULATIONS INDICATE FLOWING NODES #1001 - |
| | #1005; HOWEVER, THE PLANS SHOW NODES IN THE 300'S AND |
| | 3000'S. |
| | |
| | 10TH FLOOR: NO HYDRAULIC CALCULATIONS SUBMITTED FOR |
| | AREAS OUTSIDE THE DWELLING UNITS SUCH AS TRASH ROOMS, |
| | STORAGE ROOMS, COMMUNITY ROOMS ETC. |
| | |
| | 10TH FLOOR: PROVIDE HYDRAULIC CALCULATION FOR 4 |
| | SIDEWALL SPRINKLERS IN UNIT #1019. |
| | |
| | 10TH FLOOR: RESIDENTIAL TYPE SPRINKLERS SHOWN IN |
| | ACTIVITY ROOM #1017 AND COMMUNITY ROOM #937 (TYPICAL |
| | SEVERAL FLOORS). PER NFPA 13 SECTION 8.4.5.1 |
| | RESIDENTIAL SPRINKLERS SHALL BE PERMITTED IN DWELLING |
| | UNITS AND THEIR ADJOINING CORRIDORS. |
| | |
| | STANDPIPE RISERS: PROVIDE PRESSURE GAUGES AT THE TOP OF |
| | THE STANDPIPES PER NFPA 14 SECTION 5.5. |
| | |
| | FIRE PUMP ISOMETRIC: PER NFPA 20 (2010 EDITION) SECTION |
| | 4.14.6.3.2, THE DISTANCE OF THE FIRE PUMP SUCTION |
| | FLANGE AND ANY ADJACENT SUCTION PIPE ELBOW/TEE FLANGE |
| | SHALL BE SEPARATED BY AT LEAST 10 PIPE DIAMETERS WHEN |
| | THE ELBOW/TEE HAS A CENTERLINE PLANE PARALLEL TO A |
| | HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE: THE CODE |
| | REQUIREMENTS HAVE NOT CHANGED IN THE LATEST EDITION OF |
| | THE STANDARD; HOWEVER, DIAGRAMS OF CORRECT/INCORRECT |
| | SUCTION PIPE INSTALLATIONS HAVE BEEN UPDATED IN FIGURE |
| | A4.14.6 OF NFPA 20 - 2013 EDITION. |
| | |
| | A COMPLETE PLAN REVIEW CANNOT BE COMPLETED AT THIS TIME |
| | DUE TO SCALING AND TECHNICAL ERRORS SUBMITTED ON THE |
| | PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | DURING PLAN RESUBMISSION. |
| | |