| Plan Review Notes For Permit 16070193 |
| Permit Number |
16070193 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-04 15:56:47 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 2ND REQUEST | | | | | | 5. PROVIDE DETAILS SHOWING THE DIMENSIONS FOR | | | ACCESSIBILITY AND CLEAR FLOOR SPACE FOR ALL FIXTURES IN | | | THE BATHROOM IN SERVICE AREA. PER WPB AMEND TO FBC | | | 107.2.1 | | | SHOW MAXIMUM MINIMUM HEIGHTS FOR GRAB BARS, LAVATORY'S, | | | TOILETS, TOILET PAPER DISPENSER MIRROR AND WATER | | | FOUNTAIN ALSO KNEE AND TOE CLEARANCE. PER FBC ACC | | | CHAPTER 6 | | | | | | 6. PROVIDE LETTER ADDRESSING REQUEST FOR EXCEPTIONS | | | MUST BE APPROVED BY BUILDING OFFICIAL BEFORE PERMIT | | | WILL BE ISSUED. | | | | | | | | | | | | |
|