| Plan Review Notes For Permit 16070193 |
| Permit Number |
16070193 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-27 15:58:06 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16070193 | | | 9/27/16 | | | | | | 1) THE REQUIRED AC AND ENERGY CALCULATIONS REQUESTED IN | | | THE 1ST REVIEW WERE NOT SUBMITTED- PLEASE COMPLY. | | | | | | 2) COMMENT #3 FROM THE 1ST REVIEW STILL PARTIALLY | | | EXISTS- EXHAUST VENTILATION CALCULATIONS FOR EF-2 NOT | | | PROVIDED. | | | | | | 3) SHEET M2.1: COMMENT #4 FROM THE 1ST REVIEW STILL | | | PARTIALLY EXISTS- RECIRCULATION OF AIR FROM THE DETAIL | | | BAY TO ADJOINING AREAS IS PROHIBITED. | | | | | | 4) M2.1: COMMENT #5 FROM THE 1ST REVIEW STILL EXISTS- | | | LOCATIONS OF HAZARDOUS GAS SENSORS NOT SHOWN AND | | | APPROVED PRODUCTS NOT SUBMITTED. A) ADDITIONAL | | | INFORMATION IS REQUIRED TO DETERMINE IF THE EXHAUST | | | VENTILATION SYSTEM IS ADEQUATELY SIZED AND WILL | | | FUNCTION ACCORDING TO CODE. HYDROGEN IS INCLUDED IN THE | | | TOXIC GAS LIST ON THE NEW M4.1 SHEET. PLEASE REFER TO | | | | | | SECTION 502.4 AND CLARIFY IF HYDOGEN BATTERIES WILL BE | | | STORED IN THE DETAIL BAY OR STORAGE ROOM. PLEASE NOTE | | | CONTINOUS EXHAUST VENTILATION MAY BE REQUIRED. | | | | | | 5) M2.1: COMMENT #7 FROM THE 1ST REVIEW STILL EXISTS. | | | NO CORECTIONS HAVE BEEN MADE TO THE PLANS TO SHOW | | | REQUIRED EXHAUST VENTILATION FOR THE VEHICLE STORAGE | | | AREA. | | | | | | 6) M2.1: PLEASE SHOW THE LOCATION OF KEYED NOTE #3 ON | | | THE PLANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|