| 2016-07-25 17:05:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) INFOMATIONAL ONLY : |
| | |
| | SHEET 008 C 7 - A FDC IS LOCATED INSIDE A GATE AND A |
| | FIRE HYDRANT ON THE OTHER SIDE. ACCESS THROUGH AN OPEN |
| | GATE IS REQUIRED. |
| | |
| | IT IS STRONGLY RECCOMMENDED THAT KNOX KEY SWITCHES BE |
| | PROVIDED AT EACH GATE AND THAT ACTIVATION OF |
| | ONE(EITHER) GATE OPENS AND CLOSES BOTH. |
| | |
| | |
| | |
| | 2) INFORMATIONAL ONLY : |
| | |
| | SHEET 014 ASP - # 9 NOTE INDICATES A KNOX BOX LOCATION |
| | AS REQUIRED BY WP FIRE DEPT. |
| | |
| | KNOX KEY SWITCHES AT BOTH GATES FOR 24 HR EMERGENCY |
| | ACCESS TO THE PROPERTY AND A KNOX BOX WITH DOOR KEYS |
| | PROVIDED BY OWNER LOCATED ON THE WALL NEXT TO THE MAN |
| | DOOR ON THE NORTH SIDE OF THE BUILDING. |
| | |
| | |
| | 3) NO SHEET - I WAS UNABLE TO LOCATED A DOOR SCHEDULE |
| | TO VERIFY FIRE RATINGS AND EXIT HARDWARE. EXIT DOORS |
| | AND EXIT HARDWARE SHALL COMPLY WITH NFPA 1, CHAPTER 12 |
| | FEATURES OF FIRE PROTECTION AND NFPA 101, CHAPTER 7, |
| | MEAND OF EGRESS. |
| | |
| | 12.4 FIRE DOORS AND OTHER OPERATING PROTECTIVES. |
| | 12.4.1* THE INSTALLATION AND MAINTENANCE OF ASSEMBLIES |
| | AND DEVICES USED TO PROTECT OPENINGS IN WALLS, FLOORS, |
| | AND CEILINGS AGAINST THE SPREAD OF FIRE AND SMOKE |
| | WITHIN, INTO, OR OUT OFBUILDINGS SHALL COMPLY WITH |
| | SECTION 12.4 AND NFPA 80, STANDARD FOR FIRE DOORS AND |
| | OTHER OPENING PROTECTIVES. [80:1.1] |
| | |
| | 12.7.3 FIRE DOORS AND WINDOWS. |
| | 12.7.3.1 OPENINGS REQUIRED TO HAVE A FIRE PROTECTION |
| | RATING BY TABLE 12.7.4.2 SHALL BE PROTECTED BY |
| | APPROVED, LISTED, LABELED FIRE DOOR ASSEMBLIES AND FIRE |
| | WINDOW ASSEMBLIES AND THEIR ACCOMPANYING HARDWARE, |
| | INCLUDING ALL FRAMES, CLOSING DEVICES, ANCHORAGE, AND |
| | SILLS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| | 12.4, EXCEPT AS OTHERWISE SPECIFIED IN THIS CODE. |
| | [101:8.3.3.1] |
| | |
| | PLEASE PROVIDE A DOOR SCHEDULE LISTING THE APPLICABLE |
| | FIRE RATINGS AND EXIT HARDWARE. |
| | |
| | |
| | 4) NO SHEET - I WAS UNABLE TO LOCATE THE STAIR RAIL |
| | DETAIL. HANDRAILS SHALL COMPLY WITH NFPA 101, CHAPTER |
| | 7, MEANS OF EGRESS. 7.2.2.4 GUARDS AND HANDRAILS. |
| | 7.2.2.4.1 HANDRAILS. |
| | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| | BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 |
| | OR 7.2.2.4.1.6. |
| | |
| | 7.2.2.4.4* HANDRAIL DETAILS. |
| | 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL BE NOT LESS |
| | THAN 34 IN. (865 MM), AND NOT MORE THAN 38 IN. (965 |
| | MM), ABOVE THE SURFACE OF THE TREAD, MEASURED |
| | VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| | OF THE TREAD. |
| | |
| | 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD |
| | REQUIREMENTS. |
| | 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8 |
| | SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD |
| | FROM THE SURFACE ADJACENT THERETO. |
| | 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065 |
| | MM) HIGH, EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE |
| | PERMITTED TO BE NOT LESS THAN 36 IN. (915 MM) HIGH. |
| | (2) THE REQUIREMENT OF 7.2.2.4.5.2 SHALL NOT APPLY IN |
| | ASSEMBLY OCCUPANCIES WHERE OTHERWISE PROVIDED IN |
| | CHAPTERS 12 AND 13. |
| | |
| | PLEASE PROVIDE A SHEET DETAIL COMPLIANCE WITH THE ABOVE |
| | |
| | |
| | 5) NO SHEET - I WAS UNABLE TO LOCATE THE WIDTH |
| | DIMENSION OF THE PROPOSED INTERIOR STAIR. |
| | |
| | 7.2.2.2.1 STANDARD STAIRS. |
| | 7.2.2.2.1.1 STAIRS SHALL MEET THE FOLLOWING CRITERIA: |
| | (1) NEW STAIRS SHALL BE IN ACCORDANCE WITH TABLE |
| | 7.2.2.2.1.1(A) AND 7.2.2.2.1.2. |
| | |
| | 7.2.2.2.1.2 MINIMUM NEW STAIR WIDTH. |
| | (A) WHERE THE TOTAL OCCUPANT LOAD OF ALL STORIES SERVED |
| | BY THE STAIR IS FEWER THAN 50, THE MINIMUM WIDTH CLEAR |
| | OF ALL OBSTRUCTIONS, EXCEPT PROJECTIONS NOT MORE THAN |
| | 4? IN. (114 MM) AT OR BELOW HANDRAIL HEIGHT ON EACH |
| | SIDE, SHALL BE 36 IN. (915 MM). |
| | |
| | PLEASE PROVIDE A SHEET DETAIL COMPLIANCE WITH THE ABOVE |
| | |
| | |
| | |
| | 6) SHEET 022 A 2.2 - BASED ON THE INDICATED ROOF TRUSS |
| | DESIGN A LIGHWEIGHT ROOF TRUSS SIGN IS REQUIRED. PER |
| | FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | PLEASE PROVIDE A NOTE INDICATING COMPLIANCE ON SHEET |
| | 035 A 2.0. |
| | |
| | |
| | 7) SHEET 050 E 2.1 - CLARIFICATION IS NEEDED REGARDING |
| | NOTE # 2 AND NOTE # 4 - A NG GENERATOR AT THE NORTH |
| | EAST CORNER AND A FUEL TANK PUMP IS INDICATED ON THE |
| | SOUTH EAST CORNER. |
| | |
| | A. PLEASE PROVIDE A CONFIRMATION/VERIFICATION NOTE |
| | INDICATING IF THIS GENERATOR WILL BE PROVIDING |
| | EMERGENCY POWER FOR THE LIFE SAFETY SYSTEMS. |
| | |
| | THE GENERATOR SHALL COMPLY WITH NFPA 110, STANDARD FOR |
| | EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION. |
| | |
| | PROVIDE A NOTE INDICATING UNDER SEPARATE PERMIT. |
| | |
| | B. WHAT TYPE OF FUEL TANK IS PROPOSED? |
| | |
| | MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES |
| | SHALL COMPLY WITH NFPA 30 A, 2012 EDITION |
| | |
| | PROVIDE A NOTE INDICATING UNDER SEPARATE PERMIT. |
| | |
| | |
| | |
| | 8) SHEET 051 E 2.2 - IT IS UNCLEAR IF THE EXIT LIGHT |
| | OVER THE NORTH MAN DOOR CAN/WILL BE SEEN FROM THE |
| | WAREHOUSE AREA. |
| | |
| | PLEASE REVIEW AND VERIFY. IT IT CAN'T BE SEEN AND |
| | ADDITIONAL EXIT SIGN WILL BE NEEDED TO LEAD/DIRECT TO |
| | THAT AREA. |
| | |
| | |
| | |
| | 9) SHEET 051 E 2.2 - NO EXIT SIGN IS INDICATED OVER THE |
| | SOUTH GARAGE DOOR THAT IS PROPOSED TO BE THE 2ND EXIT. |
| | |
| | PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION. |
| | |
| | |
| | 10) SHEET 015 A 1.1 - THE SOUTH GARAGE DOOR IS |
| | INDICATED AS BEING USED AS A REQUIRED EXIT DOOR. |
| | ADDITIONAL CLARIFICATION IS NEEDED. |
| | |
| | HOW IS IT PROPOSED THAT THIS DOOR GARAGE DOOR CAN BE |
| | OPENED IN THE EVENT OF AN EMERGENCY FOR EXITING |
| | PURPOSES. PROVIDE DETAILS. |
| | |
| | PER NFPA 101, CHAPTER 42 STORAGE OCCUPANCIES , |
| | 42.2.2.2.5 WHERE HORIZONTAL OR VERTICAL SECURITY |
| | GRILLES OR DOORS ARE USED AS A PART OF THE REQUIRED |
| | MEANS OF EGRESS FROM A TENANT SPACE, SUCH GRILLES OR |
| | DOORS SHALL COMPLY WITH 7.2.1.4.1. |
| | |
| | 7.2.1.4 SWING AND FORCE TO OPEN. |
| | 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY |
| | DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE |
| | SIDE-HINGED OR PIVOTED- SWINGING TYPE, AND SHALL BE |
| | INSTALLED TO BE CAPABLE OF SWINGING FROM ANY POSITION |
| | TO THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT |
| | IS INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS: |
| | (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN |
| | CHAPTER 24, SHALL BE PERMITTED. |
| | (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE |
| | OCCUPANCIES, AS PROVIDED IN CHAPTERS 32 AND 33, SHALL |
| | BE PERMITTED. |
| | (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| | HORIZONTAL-SLIDING OR VERTICAL-ROLLING SECURITY GRILLES |
| | OR DOOR ASSEMBLIES THAT ARE PART OF THE REQUIRED MEANS |
| | OF EGRESS SHALL BE PERMITTED, PROVIDED THAT ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN |
| | SECURED IN THE FULLY OPEN POSITION DURING THE PERIOD OF |
| | OCCUPANCY BY THE GENERAL PUBLIC. |
| | (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE |
| | SHALL BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| | LESS THAN 1 IN. (25 MM) HIGH ON A CONTRASTING |
| | BACKGROUND THAT READS AS FOLLOWS: THIS DOOR TO REMAIN |
| | OPEN WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE |
| | CLOSED POSITION WHEN THE SPACE IS OCCUPIED. |
| | (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM |
| | WITHIN THE SPACE WITHOUT THE USE OF ANY SPECIAL |
| | KNOWLEDGE OR EFFORT. |
| | (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| | MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED |
| | WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR |
| | DOOR ASSEMBLIES. |
| | (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE |
| | PERMITTED UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND |
| | CORRECTIONAL OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 |
| | AND 23, SHALL BE PERMITTED. |
| | (B) HORIZONTAL-SLIDING DOOR ASSEMBLIES COMPLYING WITH |
| | 7.2.1.14 SHALL BE PERMITTED. |
| | (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43, |
| | HORIZONTALSLIDING DOOR ASSEMBLIES SERVING A ROOM OR |
| | AREA WITH AN OCCUPANT LOAD OF FEWER THAN 10 SHALL BE |
| | PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH |
| | HAZARD CONTENTS. |
| | II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER |
| | SIDE WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| | III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN |
| | THE DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 |
| | LBF (133 N) TO SET THE DOOR LEAF IN MOTION AND IS NOT |
| | MORE THAN 15 LBF (67 N) TO CLOSE THE DOOR ASSEMBLY OR |
| | OPEN IT TO THE MINIMUM REQUIRED WIDTH. |
| | IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE |
| | PROTECTION RATING, AND, WHERE RATED, IS SELF-CLOSING OR |
| | AUTOMATIC-CLOSING BY MEANS OF SMOKE DETECTION IN |
| | ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN ACCORDANCE |
| | WITH NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING |
| | PROTECTIVES. |
| | V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE |
| | SELF-LATCHING HAVE A LATCH OR OTHER MECHANISM THAT |
| | ENSURES THAT THE DOOR LEAF WILL NOT REBOUND INTO A |
| | PARTIALLY OPEN POSITION IF FORCEFULLY CLOSED. |
| | (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL |
| | AREAS, AND STORAGE AREAS WITH AN OCCUPANT LOAD NOT |
| | EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY HAZARD |
| | CONTENTS, DOOR OPENINGS TO SUCH AREAS AND PRIVATE |
| | GARAGES SHALL BE PERMITTED TO BE HORIZONTAL-SLIDING |
| | DOOR ASSEMBLIES. |
| | (5) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL |
| | AREAS, AND STORAGE AREAS WITH AN OCCUPANT LOAD NOT |
| | EXCEEDING 10 CONTAIN ONLY LOW OR ORDINARY HAZARD |
| | CONTENTS, DOOR OPENINGS TO SUCH AREAS AND PRIVATE |
| | GARAGES SHALL BE PERMITTED TO BE VERTICAL-ROLLING DOOR |
| | ASSEMBLIES. |
| | (6) REVOLVING DOOR ASSEMBLIES COMPLYING WITH 7.2.1.10 |
| | SHALL BE PERMITTED. |
| | (7) EXISTING FUSIBLE LINK?OPERATED HORIZONTAL-SLIDING |
| | OR VERTICALROLLING FIRE DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO BE USED AS PROVIDED IN CHAPTERS 39, 40, |
| | AND 42. |
| | |
| | PLEASE PROVIDE A NOTE OF NARRATIVE INDICATING |
| | COMPLAINCE, WITH DETAIL, WITH ANY OF THE ABOVE. |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |