2017-05-10 12:01:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070183
 ADD: 518 S. DIXIE HWY.
 CONT: TBD / TO BE DETERMINED
 TEL: 954-570-9500
 E-MAIL: BRIAN @ TBBG.NET
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: WED. MAY 01/ 2017
 ACTION:
  
 1A-E) COMPLETED.
  
 1F) BUILDING PROVISO/ DEFERRED SUBMITTAL. 107.3.4.2.
 THE DESIGNER OF RECORD HAS REQUESTED THE EXTERIOR
 COMPONENTS AND CLADDING TO BE A DEFERRED SUBMITTAL.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2-9) COMPLIED.
  
 10)4TH REVIEW!!!!!!!
 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 WINDOW # 7 IS 4-0 WIDE X 3-4 TALL. IF THIS IS
 CONSIDERED A DOUBLE CASEMENT WINDOW WITH THE EXTERIOR
 FRAME ON BOTH SIDES OF THE WINDOW AND THE CENTER
 VERTICAL MEMBER THE CLEAR WIDTH CANNOT BE 23.6 INCHES
 AS STATED IN THE RESPONSE! IN THE JELD WEN SERIES
 WINDOWS A OVERALL CASING (HORIZONTAL MEASUREMENT) 24
 5/16 INCHES HAS A CLEAR FRAME SIZE OF 18 INCHES.
 EMCOMPASS BY PELLA TO MEET THE MINIMUM REQUIREMENTS OF
 A CLEAR OPENING OF CLEAR OPENING OF 24 INCHES IN
 HEIGHT, 20 INCHES IN WIDTH AND THE 5.7 SQ. FT . TYPE E
 WINDOW 3-0 FT WIDE X 3-5 FT IN HEIGHT.
  
 PLEASE PROVIDE THE SIZING CHART FROM ES CASEMENT
 WINDOWS AND CIRCLE THE WINDOW SIZE AND THE CLEAR
 OPENING SIZE, THE WIDTH REQUIREMENT, HEIGHT REQUIREMENT
 AND MINIMUM CLEAR OPENING SIZE OF 5.7 SQUARE FEET. THIS
 INCLUDES THE BOTH WINDOW TYPE 7 &8.
  
  
 3RD REVIEW COMMENT. SEMI- COMPLIED. EGRESS WINDOWS
 CASEMENT SIZE 4-10X 3-4. NOTE WINDOW # 7 IS 4-0X3-4
 (DOUBLE CASEMENT WITH MULLION). PROVIDE DOCUMENTATION
 THAT THE WINDOW WILL HAVE 20 INCHES IN CLEAR WIDTH WITH
 5.7 SQUARE FEET OF VENT.
  
 10A) SHEET A-201 & A-202 PLEASE PROVIDE THE CLEAR
 OPENING SIZE FOR THE WINDOWS (VENT) FOR COMPLIANCE
 WITH: FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET.
  
 10B) FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 10C) FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 11) COMPLIED. SAFETY GLASS BATHROOM.
  
 12)4TH REVIEW. ROOF PRESSURES ARE VERY LOW, THEY ARE TO
 BE TAKEN FOR 10 SQ. FT. FOR ROOF FASTENERS. EVEN FOR A
 B EXPOSURE TAKEN AT 21.5 FT. ELEVATION AT 10 SQ. FT.
 THE ROOF PRESSURES ARE LOW.
 ROOF ZONE # 1 INDICATES -19.9 PSF SHOULD BE -31.32 VASD
 ROOF ZONE # 2 & 3 AT -35.7 PSF SHOULD BE -67.40 VASD
  
 13) 2ND REQUEST, RESTROOM IS REQUIRED ON THE 1ST FLOOR
 TENANT SPACE. . SHEET A-101 IS MISSING THE RESTROOM IN
 THE GROCERY STORE/ CONVENIENCE STORE. PLEASE REVIEW
 SECTION 1210.1 OF THE 2014 FBC-B AND 2902.1..
  
 14) COMPLIED. IMPACT FEES.
  
 15) 4TH REQUEST. WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE VOIDED SHEETS & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  