| 2017-05-10 12:01:17 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070183 |
| | ADD: 518 S. DIXIE HWY. |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 954-570-9500 |
| | E-MAIL: BRIAN @ TBBG.NET |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: WED. MAY 01/ 2017 |
| | ACTION: |
| | |
| | 1A-E) COMPLETED. |
| | |
| | 1F) BUILDING PROVISO/ DEFERRED SUBMITTAL. 107.3.4.2. |
| | THE DESIGNER OF RECORD HAS REQUESTED THE EXTERIOR |
| | COMPONENTS AND CLADDING TO BE A DEFERRED SUBMITTAL. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2-9) COMPLIED. |
| | |
| | 10)4TH REVIEW!!!!!!! |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | WINDOW # 7 IS 4-0 WIDE X 3-4 TALL. IF THIS IS |
| | CONSIDERED A DOUBLE CASEMENT WINDOW WITH THE EXTERIOR |
| | FRAME ON BOTH SIDES OF THE WINDOW AND THE CENTER |
| | VERTICAL MEMBER THE CLEAR WIDTH CANNOT BE 23.6 INCHES |
| | AS STATED IN THE RESPONSE! IN THE JELD WEN SERIES |
| | WINDOWS A OVERALL CASING (HORIZONTAL MEASUREMENT) 24 |
| | 5/16 INCHES HAS A CLEAR FRAME SIZE OF 18 INCHES. |
| | EMCOMPASS BY PELLA TO MEET THE MINIMUM REQUIREMENTS OF |
| | A CLEAR OPENING OF CLEAR OPENING OF 24 INCHES IN |
| | HEIGHT, 20 INCHES IN WIDTH AND THE 5.7 SQ. FT . TYPE E |
| | WINDOW 3-0 FT WIDE X 3-5 FT IN HEIGHT. |
| | |
| | PLEASE PROVIDE THE SIZING CHART FROM ES CASEMENT |
| | WINDOWS AND CIRCLE THE WINDOW SIZE AND THE CLEAR |
| | OPENING SIZE, THE WIDTH REQUIREMENT, HEIGHT REQUIREMENT |
| | AND MINIMUM CLEAR OPENING SIZE OF 5.7 SQUARE FEET. THIS |
| | INCLUDES THE BOTH WINDOW TYPE 7 &8. |
| | |
| | |
| | 3RD REVIEW COMMENT. SEMI- COMPLIED. EGRESS WINDOWS |
| | CASEMENT SIZE 4-10X 3-4. NOTE WINDOW # 7 IS 4-0X3-4 |
| | (DOUBLE CASEMENT WITH MULLION). PROVIDE DOCUMENTATION |
| | THAT THE WINDOW WILL HAVE 20 INCHES IN CLEAR WIDTH WITH |
| | 5.7 SQUARE FEET OF VENT. |
| | |
| | 10A) SHEET A-201 & A-202 PLEASE PROVIDE THE CLEAR |
| | OPENING SIZE FOR THE WINDOWS (VENT) FOR COMPLIANCE |
| | WITH: FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING |
| | OF 5.7 SQUARE FEET. |
| | |
| | 10B) FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET |
| | CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 |
| | MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION |
| | SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING |
| | DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF |
| | THE OPENING. |
| | |
| | 10C) FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY |
| | ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE |
| | CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM) |
| | MEASURED FROM THE FLOOR. |
| | |
| | 11) COMPLIED. SAFETY GLASS BATHROOM. |
| | |
| | 12)4TH REVIEW. ROOF PRESSURES ARE VERY LOW, THEY ARE TO |
| | BE TAKEN FOR 10 SQ. FT. FOR ROOF FASTENERS. EVEN FOR A |
| | B EXPOSURE TAKEN AT 21.5 FT. ELEVATION AT 10 SQ. FT. |
| | THE ROOF PRESSURES ARE LOW. |
| | ROOF ZONE # 1 INDICATES -19.9 PSF SHOULD BE -31.32 VASD |
| | ROOF ZONE # 2 & 3 AT -35.7 PSF SHOULD BE -67.40 VASD |
| | |
| | 13) 2ND REQUEST, RESTROOM IS REQUIRED ON THE 1ST FLOOR |
| | TENANT SPACE. . SHEET A-101 IS MISSING THE RESTROOM IN |
| | THE GROCERY STORE/ CONVENIENCE STORE. PLEASE REVIEW |
| | SECTION 1210.1 OF THE 2014 FBC-B AND 2902.1.. |
| | |
| | 14) COMPLIED. IMPACT FEES. |
| | |
| | 15) 4TH REQUEST. WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE VOIDED SHEETS & REPLACE |
| | ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING |
| | THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION |
| | OF THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |