| Plan Review Notes For Permit 16070183 |
| Permit Number |
16070183 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-02-15 10:20:08 | 518 SOUTH DIXIE HIGHWAY | | | PERMIT #16070183 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE PROTECTION SPRINKLER PLANS REFERENCE THE CIVIL | | | PLANS FOR THE NEW UNDERGROUND FIRE MAIN AND BACKFLOW | | | PREVENTER; HOWERVER, NO CIVIL PLANS WERE SUBMITTED WITH | | | THIS DRAWING SET. | | | | | | FIRE SPRINKLER SYSTEM (BACKFLOW PREVENTER, FLOW | | | SWITCHES, TAMPER SWITCHES, MONITORING PANEL) NEEDS TO | | | BE COORDINATED WITH THE ELECTRICAL DESIGN. | | | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED FOR CENTRAL | | | STATION SERVICE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] |
|