| 2016-12-13 10:29:17 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | ORIGINAL COMMENTS: |
| | |
| | NOT COMPLIED 1) INDICATE THE OCCUPANCY GROUPS ON THE |
| | PLAN IN ACCORDANCE WITH CHAPTER 3 OF FBC. |
| | |
| | NOT COMPLIED 2) SUBMIT AN EXISTING FIRST FLOOR PLAN. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | NOT COMPLIED 3) SHT. A-103. SHOW THE WIDTH OF THE |
| | SHOWERS. COMPLY WITH FPC SEC.417.4 |
| | |
| | NOT COMPLIED 6) THE BACKFLOW PREVENTERS SHALL BE |
| | LOCATED AT THE WATER METERS PER THE CWP CROSS |
| | CONNECTION CONTROL MANUAL. |
| | NOT COMPLIED 7) THE PLAN CALLS OUT A 2 INCH UNDERGROUND |
| | COLD WATER LINE BUT THE LINE IS LABELED AS A CONDENSATE |
| | DRAIN. CLARIFY. THERE IS NOTES REMAINING ON CONDENSATE |
| | LINE WHICH ARE CALLING IT A COLD WATER LINE. |
| | NOT COMPLIED 8) SHT. A101 CALLS OUT FOR THE EXISTING |
| | GREASE TRAP TO BE REPLACED OR RELOCATED & SHT.P1.1 |
| | INDICATES IT IS TO REMAIN. WHICH IS IT? CLARIFY. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT A-101 IS THE BATHROOM EXISTING IF IT IS NEW OR |
| | RELOCATED PROVIDE PLUMBING RISER. AND NOTE ON PLAN. WPB |
| | AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 2. PROVIDE MOUNTING DETAILS FOR GRAB BARS TO COMPLY |
| | WITH. FBC ACC 604.5.1/ |
| | 604.5.2 /609.4 |
| | |
| | |
| | |
| | |