2016-12-13 10:29:172ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 ORIGINAL COMMENTS:
  
 NOT COMPLIED 1) INDICATE THE OCCUPANCY GROUPS ON THE
 PLAN IN ACCORDANCE WITH CHAPTER 3 OF FBC.
  
 NOT COMPLIED 2) SUBMIT AN EXISTING FIRST FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOT COMPLIED 3) SHT. A-103. SHOW THE WIDTH OF THE
 SHOWERS. COMPLY WITH FPC SEC.417.4
  
 NOT COMPLIED 6) THE BACKFLOW PREVENTERS SHALL BE
 LOCATED AT THE WATER METERS PER THE CWP CROSS
 CONNECTION CONTROL MANUAL.
 NOT COMPLIED 7) THE PLAN CALLS OUT A 2 INCH UNDERGROUND
 COLD WATER LINE BUT THE LINE IS LABELED AS A CONDENSATE
 DRAIN. CLARIFY. THERE IS NOTES REMAINING ON CONDENSATE
 LINE WHICH ARE CALLING IT A COLD WATER LINE.
 NOT COMPLIED 8) SHT. A101 CALLS OUT FOR THE EXISTING
 GREASE TRAP TO BE REPLACED OR RELOCATED & SHT.P1.1
 INDICATES IT IS TO REMAIN. WHICH IS IT? CLARIFY.
  
 NEW COMMENTS:
  
 1. SHT A-101 IS THE BATHROOM EXISTING IF IT IS NEW OR
 RELOCATED PROVIDE PLUMBING RISER. AND NOTE ON PLAN. WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 2. PROVIDE MOUNTING DETAILS FOR GRAB BARS TO COMPLY
 WITH. FBC ACC 604.5.1/
 604.5.2 /609.4
  
  
  
  