2016-12-03 11:02:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070183
 ADD: 518 S. DIXIE HWY.
 CONT: TBD / TO BE DETERMINED
 TEL: 954-570-9500
 E-MAIL: BRIAN @ TBBG.NET
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. DEC. 03/ 2016
 ACTION: DENIED
  
 1A)2ND REQUEST. THE BUILDING TYPE HAS NOT CHANGED, THE
 RESPONSE INDICATES CHANGED FROM A BUILDING TYPE VA TO
 VB. PLEASE PROVIDE WHAT YOU ARE DEFINING AS A
 PROTECTED. THE DESIGNER OF RECORD CLASSIFIES THE TWO
 BUILDINGS AS A SINGLE BUILDING ON THE SAME LOT, NOT
 REQUIRING THE OPENINGS TO BE PROTECTED BETWEEN
 BUILDINGS, OR ARE YOU REFERRING TO THE REQUIRED
 PROTECTION PER TABLE 602, THE CLOSENESS TO THE PROPERTY
 LINE OR THE 1ST FLOOR REAR EXITING AND THE CLOSENESS OF
 THE 2ND BUILDING ON THE SAME LOT REQUIRING A CREATING
 AN EXIT COURT IN COMPLIANCE WITH 2014 FBC-B 1027.4.2
 EGRESS COURT CONSTRUCTION AND OPENINGS.
 1ST ROUND COMMENT.
 SHEET A-001 THE COVERSHEET INDICATES UNDER THE HEADING
 OF KEY PROJECT DATA THIS BUILDING IS A CONSTRUCTION
 TYPE (VB) PROTECTED. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED. NORMALLY THE TERM PROTECTED IS USED AS A
 FIRE RATING OF STRUCTURAL MEMBERS, AS IN BUILDING TYPE
 1A, 1B, IIA, IIIA, IVA OR VA.
 SEE TABLE 601 FOR FIRE RATINGS OF STRUCTURAL ELEMENTS.
  
 1B) COMPLIED / 2 BUILDINGS ON THE SAME LOT. FBC-B
 503.1.2.
  
 1C) 2ND REQUEST, THIS COMMENT DEALS WITH HORIZONTAL
 FIRE BARRIER REQUIREMENTS!!!! PROVIDE AN FLOOR/CEILING
 ASSEMBLY !!! THANK YOU. DON?T JUST PUT A FIRE RATING ON
 THE PLANS SHOWING COMPLIANCE.
 1ST ROUND OF COMMENTS.
 SHEET A-001 UNDER THE HEADING KEY PROJECT DATA DOES NOT
 LIST THE REQUIREMENTS FOR SEPARATING OCCUPANCIES WITH
 HORIZONTAL FIRE BARRIER REQUIREMENTS. SHEET A-101
 INDICATES 1 HOUR SEPARATION. SEE FBC-B SECTION 707.3.10
 FIRE AREAS. THE FIRE BARRIERS OR HORIZONTAL ASSEMBLIES,
 OR BOTH. THE FIRE BARRIERS OR HORIZONTAL ASSEMBLIES, OR
 BOTH, SEPARATING FIRE AREAS OF MIXED OCCUPANCIES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN THE
 HIGHEST VALUE INDICATED IN TABLE 707.3.10 FOR THE
 OCCUPANCIES UNDER CONSIDERATION, 2 HOUR FIRE RATING.
  
 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 1D) 2ND REQUEST. THE RESPONSE INDICATES A FIRE
 SPRINKLER SYSTEM SHALL BE ADDED TO THE NEW APARTMENT ON
 RCP SHEET A-104. PLEASE REFER BACK TO THE REQUIREMENTS
 OF A LEVEL II ALTERATION UNDER 804.2.2. 804.2.2
 R-2, IN BUILDINGS WITH OCCUPANCIES IN GROUPS A, B, E,
 F-1, H, I, M, R-1, R-2, R-4, S-1 AND S-2, WORK AREAS
 THAT HAVE EXITS OR CORRIDORS SHARED BY MORE THAN ONE
 TENANT OR THAT HAVE EXITS OR CORRIDORS SERVING AN
 OCCUPANT LOAD GREATER THAN 30 SHALL BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION WHERE ALL OF THE
 FOLLOWING CONDITIONS OCCUR:
 (1.) THE WORK AREA IS REQUIRED TO BE PROVIDED WITH
 AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING AS APPLICABLE TO NEW
 CONSTRUCTION; AND
 (2.) THE WORK AREA EXCEEDS 50 PERCENT OF THE FLOOR
 AREA.
 THIS ADDITION AND RENOVATION MEETS BOTH REQUIREMENTS,
 THE R2 FIRE AREA NEW AND OLD MUST BE FIRE SPRINKLERED.
  
 1ST ROUND COMMENT. SHEET A-001 UNDER THE HEADING KEY
 PROJECT DATA INDICATES THE BUILDING IS NON-SPRINKLERED
 BUILDING. THE 2014 EXISTING BUILDING CODE SECTION
 1102.3 FIRE PROTECTION SYSTEMS. EXISTING FIRE AREAS
 INCREASED BY THE ADDITION SHALL COMPLY WITH CHAPTER 9
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-B 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 1E) SEMI-COMPLIED. 2ND REVIEW PLEASE REVIEW SHEETS
 A-202 VERSES A-507. SHEET A-507 IT STILL APPEARS THIS
 IS AN OPEN STAIR WITH A GUARDRAIL BUT A-107 (2ND FLOOR)
 & A-202 IT WOULD APPEAR THE OUTSIDE WALL IS A FULLY
 ENCLOSED WALL WITH AN EXTERIOR EGRESS DOOR AT THE
 BOTTOM OF THE STAIR WITH AN EXIT DOORWAY? REQUIRING
 GUARDRAILS ON BOTH SIDES OF THE NEW STAIRWELL. 2014
 FBC-B 1009.15 HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS
 ON EACH SIDE OF THE STAIR ENCLOSRE AND SHALL COMPLY
 WITH SECTION 1012.
  
 1ST ROUND COMMENTS. PLEASE PROVIDE A LIFE SAFETY PLAN.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN 107.3.5.1
 COMMERCIAL BUILDINGS:
  
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 GUARDS/ HANDRAILS/ DESIGN LOADS
  
  
  
  
 1F) BUILDING PROVISO/ DEFERRED SUBMITTAL. 107.3.4.2.
 THE DESIGNER OF RECORD HAS REQUESTED THE EXTERIOR
 COMPONENTS AND CLADDING TO BE A DEFERRED SUBMITTAL.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SEMI-COMPLIED. SHEET A-103 NOW SHOWS THE OPENINGS ON
 THE NORTH WALL HAVING GLASS BLOCK IN THE OPENINGS, THE
 PLANS INDICATE THIS AS OPENING # 3, REPLACE WITH FIRE
 RATED GLASS BLOCK MASONRY. THERE IS NO MENTION AS TO
 THE REQUIRED FIRE RATING THAT IS REQUIRED. 706.6.1
 STEPPED BUILDINGS.
  
 1ST ROUND OF COMMENTS. SHEET A-103 SHOWS A VERTICAL
 ADDITION. AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS. 2014 EXISTING BUILDING CODE. THE NORTH WALL OF
 THE EXISTING 2 STORY IS LESS THAN 3 FEET FROM THE
 PROPERTY LINE WALL. THE 2014 FBC-B TABLE 705.8 MAXIMUM
 AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. 0-3 FEET
 THERE ARE NO OPENINGS ALLOWED.
  
 2014 FBC-B 706.6.1 STEPPED BUILDINGS. WHERE A FIRE WALL
 SERVES AS AN EXTERIOR WALL FOR A BUILDING AND SEPARATES
 BUILDINGS HAVING DIFFERENT ROOF LEVELS, SUCH WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 30 INCHES ABOVE THE
 LOWER ROOF LEVEL, PROVIDED THE EXTERIOR WALL FOR A
 HEIGHT OF 15 FEET ABOVE THE LOWER ROOF IS NOT LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION FROM BOTH
 SIDES WITH OPENINGS PROTECTED BY FIRE ASSEMBLIES HAVING
 A FIRE PROTECTION RATING OF NOT LESS THAN 3/4 HOUR.
  
 THE DESIGNER OF RECORD MAY CLOSE THESE OPENINGS IN WITH
 1 HOUR FIRE RATED CONSTRUCTION AS PER TABLE 602 OF THE
 FBC-B, INSTALL 3/4 HOUR FIRE RATED GLASS BLOCK, OR A 1
 HOUR FIRE SHUTTER ON THE EXTERIOR OF THE WALL.
  
 3) SEMI- COMPLIED. THE DESIGNER OF RECORD NOW INDICATES
 ON THE PLANS A 2 HOUR RATED CEILING ASSEMBLY BUT THERE
 IS NO GYPSUM ASSOCIATION, OR UL LISTED ASSEMBLY IN THE
 PLANS FOR THE RATING OF THE CEILING FOR EITHER 1 OR 2
 HOUR. THE CODE ONLY REQUIRES THE CEILING UNDER THE
 STAIR TO BE 1 HOUR, THE DESIGNER CAN DESIGN TO THE MORE
 STRINGENT 2 HOUR FIRE REQUIREMENT.
  
 1ST ROUND OF COMMENTS. SHEET A-101 SHOWS UNDER THE
 ENCLOSED STAIRWELL A CLOSET. THE PLANS DO NOT INDICATE
 HOW COMPLIANCE WITH SECTION 1009.9.3 WILL BE OBTAINED.
 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 4-9) COMPLIED.
  
 10) COMPLIED. EGRESS WINDOWS CASEMENT SIZE 4-10X 3-4.
  
 11) 2ND REQUEST. WINDOW NEXT TO TUB IS INDICATED IN THE
 RESPONSE SHALL BE CATEGORY II SAFETY GLASS, BUT THIS
 STATEMENT IS NOT FOUND ON SHEET A-103 WINDOW # 9. ONLY
 FROSTED GLASS.
  
 1ST ROUND OF COMMENTS.
 SHEET A-103 THE REAR APARTMENT WITH THE TUB NEXT TO THE
 EXTERIOR WALL AND WINDOW, PLEASE PROVIDE SILL HEIGHT
 AND COMPLIANCE WITH: FBC-B 2406.4.5 GLAZING AND WET
 SURFACES. GLAZING IN WALLS, ENCLOSURES OR, BATHTUBS,
 SHOWERS WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS
 LESS THAN 60 INCHES MEASURED VERTICALLY ABOVE ANY
 STANDING OR WALKING SURFACE SHALL BE CONSIDERED A
 HAZARDOUS LOCATION. THIS SHALL APPLY TO SINGLE GLAZING
 AND ALL PANES IN MULTIPLE GLAZING.
  
 12)2ND REQUEST. SHEET S-102 THE MEAN ROOF HEIGHT IS
 GIVEN AT < 15 FEET MEAN ROOF HEIGHT. IN SCALING THE
 PLANS IT APPEARS THE ROOF HEIGHT IS 22 FEET AND THE TOP
 OF PARAPET IS 24-9. PLEASE PROVIDE WHERE THE WINDOW,
 DOOR AND ROOF PRESSURES CAN BE FOUND FOR ZONES 1,2,3,4
 & 5. PLEASE PROVIDE THEM IN VASD SINCE THE PRODUCT
 APPROVALS ARE IN VASD.
  
 1ST ROUND OF COMMENTS. NEITHER THE ELEVATION SHEETS NOR
 THE STRUCTURAL SHEETS PROVIDE THE WIND DESIGN CRITERIA
 NOR PRESSURES.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO