Plan Review Notes
Plan Review Notes For Permit 16070183
Permit Number 16070183
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-17 10:34:011) INDICATE THE OCCUPANCY GROUPS ON THE PLAN IN
 ACCORDANCE WITH CHAPTER 3 OF FBC.
 2) SUBMIT AN EXISTING FIRST FLOOR PLAN. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHT. A-103. SHOW THE WIDTH OF THE SHOWERS. COMPLY
 WITH FPC SEC.417.4
 4) ACCESS SHALL BE PROVIDED TO THE SHUTOFF VALVES FOR
 THE STACKED WASHER/DRYER UNITS. FPC SEC.606.3.
 5) SHT.P1.1 - THE PLANS CALL OUT NEW 1 INCH COLD WATER
 PIPE IN CEILING BUT THE LINE IS LABELED AS A CONDENSATE
 LINE. THIS OCCURS IN SVERAL PLACES. CLARIFY.
 6) THE BACKFLOW PREVENTERS SHALL BE LOCATED AT THE
 WATER METERS PER THE CWP CROSS CONNECTION CONTROL
 MANUAL.
 7) THE PLAN CALLS OUT A 2 INCH UNDERGROUND COLD WATER
 LINE BUT THE LINE IS LABELED AS A CONDENSATE DRAIN.
 CLARIFY.
 8) SHT. A101 CALLS OUT FOR THE EXISTING GREASE TRAP TO
 BE RREPLACED OR RELOCATED & SHT.P1.1 INDICATES IT IS TO
 REMAIN. WHICH IS IT? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  