| Plan Review Notes For Permit 16070183 |
| Permit Number |
16070183 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-17 10:34:01 | 1) INDICATE THE OCCUPANCY GROUPS ON THE PLAN IN | | | ACCORDANCE WITH CHAPTER 3 OF FBC. | | | 2) SUBMIT AN EXISTING FIRST FLOOR PLAN. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 3) SHT. A-103. SHOW THE WIDTH OF THE SHOWERS. COMPLY | | | WITH FPC SEC.417.4 | | | 4) ACCESS SHALL BE PROVIDED TO THE SHUTOFF VALVES FOR | | | THE STACKED WASHER/DRYER UNITS. FPC SEC.606.3. | | | 5) SHT.P1.1 - THE PLANS CALL OUT NEW 1 INCH COLD WATER | | | PIPE IN CEILING BUT THE LINE IS LABELED AS A CONDENSATE | | | LINE. THIS OCCURS IN SVERAL PLACES. CLARIFY. | | | 6) THE BACKFLOW PREVENTERS SHALL BE LOCATED AT THE | | | WATER METERS PER THE CWP CROSS CONNECTION CONTROL | | | MANUAL. | | | 7) THE PLAN CALLS OUT A 2 INCH UNDERGROUND COLD WATER | | | LINE BUT THE LINE IS LABELED AS A CONDENSATE DRAIN. | | | CLARIFY. | | | 8) SHT. A101 CALLS OUT FOR THE EXISTING GREASE TRAP TO | | | BE RREPLACED OR RELOCATED & SHT.P1.1 INDICATES IT IS TO | | | REMAIN. WHICH IS IT? CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|