Plan Review Notes
Plan Review Notes For Permit 16070183
Permit Number 16070183
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-15 10:11:591ST REVIEW MECHANICAL
 PERMIT #16070183
 7/15/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MINI-SPLIT SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.4.3 & C401.2 FBC-14 ENERGY CONSERVATION.
  
 3) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 DRYER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 504.5, 504.6.4. INDICATE THE TYPE OF EXHAUST DUCT WORK
 AND GAUGE OF STEEL
  
 4) PROVIDE UL LISTED FIRESTOPPING ASSEMBLIES FOR AC
 REFRIGERANT AND CONDENSATE PIPING PENETRATING
 FIRE-RATED FLOOR/CEILING AND WALL ASSEMBLIES.
  
 5) INDICATE THE TYPE AND THICKNESS OF REFRIGERANT AND
 CONDENSATE PIPING INSULATION ON THE PLAN, AND PROVIDE A
 SUBMITTAL.
  
 6) M0.1: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 COMPLETE DETAILS FOR ATTACHMENT AND ANCHORING OF THE
 CONDENSER UNITS AND ROOF STAND. SUBMIT A FL. PRODUCT
 APPROVAL FOR THE STAND WITH APPROVAL SIGNATURE BY THE
 DESIGN PROFESSIONAL OF RECORD. PLEASE CIRCLE,
 HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE DETAILS,
 NOTES, DESIGN PRESSURES SHOWN ON THE DOCUMENT- SECTION
 301.15.
  
 7) IT APPEARS THAT A PERMANENT LADDER WILL BE REQUIRED
 TO PROVIDE ACCESS TO THE ROOFTOP MECHANICAL EQUIPMENT.
 REFER TO SECTION 306.5 AND SHOW THE LOCATION OF THE
 LADDER, AND PROVIDE CONSTRUCTION DETAILS.
  
 8) THERE ARE NO DIMESIONS ON THE ELEVATION DRAWINGS OR
 PARAPET SECTIONS TO INDICATE THE HEIGHT OF THE PARAPET
 ABOVE THE FINISHED ROOF SURFACE. PLEASE REVIEW AND
 PROVIDE GUARDS AT THE ROOF EDGES WHERE NECESSARY AS
 REQUIRED BY SECTION 304.11.
  
 9) CLARIFY HOW ACCESS FOR MAINTENANCE AND REPLACEMENT
 OF THE DRYER MAKEUP AIR MOTORIZED DAMPER WILL BE
 PROVIDED- SEE SECTION 306.1.
  
 10) SHEET A-105 SHOWS A MECHANICAL CHASE MOST LIKELY
 FOR A KITCHEN EXHAUST DUCT. PLEASE NOTE THAT THE DUCT
 MUST BE INSPECTED BEFORE BEING ENCLOSED IN THE CHASE,
 AND A UL APPROVED FIRESTOPPING ASSEMBLY WILL BE
 REQUIRED WHERE THE DUCT EXITS THE BOTTOM OF THE CHASE
 AT CEILING LEVEL. PLEASE ALSO NOTE THAT GREASE DUCTS
 REQUIRE AN 18" CLEARANCE TO COMBUSTIBLES PER SECTION
 506.3.6.
  
 11) PLEASE PROVIDE A RESPONSE NARRATIVE FROM THE DESIGN
 PROFESSIONAL ADDRESSING ALL OF THE COMMENTS LISTED
 ABOVE, A) ALL MECHANICAL EQUIPMENT AND APPLIANCE
 SUBMITTALS SHALL BEAR THE APPROVAL SIGNATURE OF THE
 DESIGN PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  