| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | GENERARL: THE BUILDING IS FUNCTIONING AS A MULTIUSE |
| | OCCUPANCY. INDICATE IF THE BUILDING IS DESIGNED FOR |
| | MIXED USE (NON-SEPARATED) OR SEPARATED USE PER SECTION |
| | 6.1.14.2.1 OF NFPA 101 FLORIDA EDITION 2012. FOR |
| | NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST STRINGENT |
| | FIRE AND LIFE SAFETY REQUIREMENTS OF EACH OCCUPANCY |
| | SHALL APPLY TO THE BUILDING. |
| | |
| | GENERAL: PROVIDE A LIFE SAFETY PLAN SHOWING ALL |
| | OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS, |
| | EXITS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL |
| | DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | |
| | GENERAL: PROVIDE A DETAILED SITE. |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: PER NPFA 1 SECTION 8.3.2.4, EACH FIRE BARRIER |
| | SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS. |
| | CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND |
| | HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT |
| | MORE THAN 15 FEET ON CENTER. |
| | |
| | GENERAL: PER SECTION 7.2.2.6.3 THE OUTSIDE STAIRS MAY |
| | NEED TO BE PROTECTED FROM FIRE EXPOSURE DEPENDING UPON |
| | OPENING PROTECTIVES AND SPRINKLER PROTECTION OF |
| | ADJACENT BUILDING. |
| | |
| | GENERARL: NO STAIR OR HANDRAIL DETAILS SUBMITTED. |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 |
| | INCHES IN HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND |
| | HAVE A MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE |
| | ACCUMULATION OF WATER. |
| | |
| | SHEET A-001: PROJECT DATA INDICATES THIS BUILDING IS |
| | NOT PROTECTED BY AUTOMATIC FIRE SPRINKLERS. ALL NEW |
| | APARTMENTS REQUIRE THE ENTIRE BUILDING TO BE PROTECTED |
| | THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM PER SECTION 30.3.5. PER SECTION |
| | 43.8.1.2, AN ADDITION SHALL NOT CREATE OR EXTEND ANY |
| | NONCONFORMITY WITH REGARD TO FIRE SAFETY OR THE MEANS |
| | OF EGRESS IN THE EXISTING BUILDING FOR WHICH THE |
| | ADDITION IS CONSTRUCTED. FOR ISSUANCE OF A GENERAL |
| | BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| | BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | SHEET A-103: NO DOOR SCHEDULE PROVIDED. PER SECTION |
| | 30.3.6.2.1 DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS |
| | SHALL HAVE NOT LESS THAN A 20-MINUTE FIRE PROTECTION |
| | RATING AND SHALL BE SELF CLOSING AND SELF LATCHING. |
| | |
| | SHEET E1.1 & E1.2: NO INTERIOR OR EXTERIOR STAIR |
| | LIGHTING PROVIDED. PER SECTION 7.8.1.3 THE FLOORS AND |
| | OTHER WALKING SURFACES WITHIN AN EXIT AND WITHIN THE |
| | PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE |
| | DESIGNATED SHALL BE ILLUMINATED AS FOLLOWS: |
| | (1) DURING CONDITIONS OF STAIR USE, THE MINIMUM |
| | ILLUMINATION FOR STAIRS SHALL BE AT LEAST 10 FT-CANDLE |
| | (108 LUX), MEASURED AT THE WALKING SURFACES. |
| | |
| | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED DURING PLAN RESUBMISSION. |
| | |