| 2016-07-13 15:10:07 | 1ST ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | 1. PER FBC-B SECTION 1006.1 YOU ARE REQUIRED TO HAVE |
| | ILLUMINATION FOR THE MEANS OF EGRESS. THIS ILLUMINATION |
| | SHALL BE PROVIDED WITH EMERGENCY BACK-UP POWER AS |
| | INDICATED IN FBC-B SECTION 1006.3. THIS INCLUDES BOTH |
| | EXIT STAIRS AND ALL THE WAY TO THE PUBLIC WAY. |
| | 2. FBC-EX SECTION 1101.2: THE EXTENT OF ALTERATIONS |
| | BEING CONDUCTED PROMOTES ADDITIONAL LIFE SAFETY |
| | REQUIREMENTS FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | SEE FIRE REVIEW FOR FURTHER DETAILS. |
| | 3. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED ABOUT |
| | ELECTRICAL EQUIPMENT. THIS MEANS THAT YOU SHALL PROVIDE |
| | LIGHTING ADJACENT TO THE ELECTRICAL PANEL OF UNITS B & |
| | C. |
| | 4. PER FBC-B 714.3.2 EXCEPTIONS: 1.1 UNLESS YOU HAVE |
| | SOLID NONCOMMUNICATING PARTITIONS, ALL ELECTRICAL BOXES |
| | IN 2 HR. RATED WALLS SHALL BE PROTECTED WITH LISTED |
| | FIRE STOPPING MATERIAL. |
| | 5. NOTE WHETHER UNDER SEPARATE PERMIT OR OTHERWISE, THE |
| | SERVICE CHANGE HAS TO BE MADE A PART OF THIS PROJECT AS |
| | THE EXISTING SERVICE IS NONCOMPLIANT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| | |