2016-08-02 16:56:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070183
 ADD: 518 S. DIXIE HWY.
 CONT: TBD / TO BE DETERMINED
 TEL: 954-570-9500
 E-MAIL: BRIAN @ TBBG.NET
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 02/ 2016
 ACTION: DENIED
  
 1A) SHEET A-001 THE COVERSHEET INDICATES UNDER THE
 HEADING OF KEY PROJECT DATA THIS BUILDING IS A
 CONSTRUCTION TYPE (VB) PROTECTED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. NORMALLY THE TERM PROTECTED IS
 USED AS A FIRE RATING OF STRUCTURAL MEMBERS, AS IN
 BUILDING TYPE 1A, 1B, IIA, IIIA, IVA OR VA.
 SEE TABLE 601 FOR FIRE RATINGS OF STRUCTURAL ELEMENTS.
  
 1B) SHEET A-001 UNDER THE KEY PROJECT DATA DOES NOT
 ADDRESS THE ISSUE OF THE CLOSENESS OF THE 2 BUILDINGS
 ON THE SAME LOT AND ALLOWABLE OPENINGS VERSES ASSUMED
 PROPERTY LINES VERSES 503.1.2 BUILDINGS ON THE SAME
 LOT. FBC-B 503.1.2.
  
 1C) SHEET A-001 UNDER THE HEADING KEY PROJECT DATA DOES
 NOT LIST THE REQUIREMENTS FOR SEPARATING OCCUPANCIES
 WITH HORIZONTAL FIRE BARRIER REQUIREMENTS. SHEET A-101
 INDICATES 1 HOUR SEPARATION. SEE FBC-B SECTION 707.3.10
 FIRE AREAS. THE FIRE BARRIERS OR HORIZONTAL ASSEMBLIES,
 OR BOTH. THE FIRE BARRIERS OR HORIZONTAL ASSEMBLIES, OR
 BOTH, SEPARATING FIRE AREAS OF MIXED OCCUPANCIES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN THE
 HIGHEST VALUE INDICATED IN TABLE 707.3.10 FOR THE
 OCCUPANCIES UNDER CONSIDERATION, 2 HOUR FIRE RATING.
  
 420.3 HORIZONTAL SEPARATION. FLOOR ASSEMBLIES
 SEPARATING DWELLING UNITS IN THE SAME BUILDINGS, FLOOR
 ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME
 BUILDING AND FLOOR ASSEMBLIES SEPARATING DWELLING OR
 SLEEPING UNITS FROM OTHER OCCUPANCIES CONTIGUOUS TO
 THEM IN THE SAME BUILDING SHALL BE CONSTRUCTED AS
 HORIZONTAL ASSEMBLIES IN ACCORDANCE WITH SECTION 711.
  
 1D) SHEET A-001 UNDER THE HEADING KEY PROJECT DATA
 INDICATES THE BUILDING IS NON-SPRINKLERED BUILDING. THE
 2014 EXISTING BUILDING CODE SECTION 1102.3 FIRE
 PROTECTION SYSTEMS. EXISTING FIRE AREAS INCREASED BY
 THE ADDITION SHALL COMPLY WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2014 FBC-B 903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA.
  
 1E) PLEASE PROVIDE A LIFE SAFETY PLAN. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
  
  
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS A LIFE SAFETY FLOOR PLAN WITH:
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 GUARDS/ HANDRAILS/ DESIGN LOADS
 DOORS PROVIDE DOOR SCHEDULE
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 1F) THE DESIGNER OF RECORD HAS REQUESTED THE EXTERIOR
 COMPONENTS AND CLADDING TO BE A DEFERRED SUBMITTAL.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SHEET A-103 SHOWS A VERTICAL ADDITION. AN ADDITION
 SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE
 EXISTING BUILDING TO WHICH THE ADDITION IS BEING MADE
 WITH REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING, OR ELECTRICAL SYSTEMS. 2014 EXISTING BUILDING
 CODE. THE NORTH WALL OF THE EXISTING 2 STORY IS LESS
 THAN 3 FEET FROM THE PROPERTY LINE WALL. THE 2014 FBC-B
 TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS
 BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING
 PROTECTION. 0-3 FEET THERE ARE NO OPENINGS ALLOWED.
  
 2014 FBC-B 706.6.1 STEPPED BUILDINGS. WHERE A FIRE WALL
 SERVES AS AN EXTERIOR WALL FOR A BUILDING AND SEPARATES
 BUILDINGS HAVING DIFFERENT ROOF LEVELS, SUCH WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 30 INCHES ABOVE THE
 LOWER ROOF LEVEL, PROVIDED THE EXTERIOR WALL FOR A
 HEIGHT OF 15 FEET ABOVE THE LOWER ROOF IS NOT LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION FROM BOTH
 SIDES WITH OPENINGS PROTECTED BY FIRE ASSEMBLIES HAVING
 A FIRE PROTECTION RATING OF NOT LESS THAN 3/4 HOUR.
  
 THE DESIGNER OF RECORD MAY CLOSE THESE OPENINGS IN WITH
 1 HOUR FIRE RATED CONSTRUCTION AS PER TABLE 602 OF THE
 FBC-B, INSTALL 1 HOUR FIRE RATED GLASS BLOCK, OR A 1
 HOUR FIRE SHUTTER ON THE EXTERIOR OF THE WALL.
  
 3) SHEET A-101 SHOWS UNDER THE ENCLOSED STAIRWELL A
 CLOSET. THE PLANS DO NOT INDICATE HOW COMPLIANCE WITH
 SECTION 1009.9.3 WILL BE OBTAINED. 2014 FBC-B 1009.9.3
 ENCLOSURES UNDER INTERIOR STAIRWAYS.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 4) SHEET A-101, A-103 & A-104 ALL SHOW A NEW EXTERIOR
 STAIR. THE PLANS DO NOT SHOW COMPLIANCE WITH SECTION
 1026 OF THE 2014 FBC-B. 1026.6 EXTERIOR STAIRWAY AND
 RAMP PROTECTION.
 EXTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1022.2. OPENINGS SHALL BE LIMITED TO THOSE
 NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES.
 PLEASE ALSO SEE THE 2012 IBC COMMENTARY 1026.6 AND
 FIGURE 1026.6(1) FOR ALLOWABLE OPENINGS AND REQUIRED
 FIRE RATINGS. PLEASE NOTE THIS AFFECTS ALL OPENINGS 1ST
 & 2ND FLOORS THAT ARE WITHIN 10 FEET OF THE STAIR&
 LANDINGS ON BOTH BUILDINGS!!!!!
  
 5) SHEET A-101: THE 2ND STORY R2 OCCUPANCY EGRESS STAIR
 OPENS SWINGING OUT OVER THE PROPERTY LINE.
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 6) SHEET A-101 THE NEW PROPOSED DELI DOES NOT SHOW ANY
 EGRESS DOORS THAT OPEN ONTO DIXIE HWY. THERE IS A PAIR
 OF DOORS OUT THE BACK OF THE PROPOSED DELI BUT WOULD
 NEED TO MEET THE REQUIREMENTS FOR EGRESS COURTS,
 SECTION FBC-B 1027.4.(1-5).
  
 7) SHEET A-103 SHOWS A WALL TYPE LEGEND WITH VARIOUS UL
 LISTINGS. PLEASE PROVIDE THE WHOLE UL LISTING SO THE
 INSPECTORS WILL HAVE DOCUMENTATION IN THE FIELD WHAT
 MAKES UP THE WALL ASSEMBLY. 703.2 FIRE-RESISTANCE
 RATINGS.
  
 8) THE 2ND FLOOR CORRIDOR WALLS WILL NEED TO SHOW
 COMPLIANCE WITH 2014 FBC-B 1018.6 CORRIDOR CONTINUITY.
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF
 EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR
 TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT
 ACCESS STAIRWAYS OR RAMPS, THE FIRE RESISTANCE-RATING
 SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR
 RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON
 THE ADJACENT FLOOR LEADING TO THE EXIT.
  
 9) SHEET A-105 SHOWS ROOF TOP EQUIPMENT ON THE ROOF OF
 THE SECOND STORY PLEASE SHOW COMPLIANCE WITH: FBC-B
 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL
 BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS,
 THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL
 TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED FOR ROOF TOP ACCESS.
  
 10A) SHEET A-201 & A-202 PLEASE PROVIDE THE CLEAR
 OPENING SIZE FOR THE WINDOWS (VENT) FOR COMPLIANCE
 WITH: FBC-B 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING
 OF 5.7 SQUARE FEET.
  
 10B) FBC-B 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610
 MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION
 SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING
 DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF
 THE OPENING.
  
 10C) FBC-B 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE
 CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM)
 MEASURED FROM THE FLOOR.
  
 11) SHEET A-103 THE REAR APARTMENT WITH THE TUB NEXT TO
 THE EXTERIOR WALL AND WINDOW, PLEASE PROVIDE SILL
 HEIGHT AND COMPLIANCE WITH: FBC-B 2406.4.5 GLAZING AND
 WET SURFACES. GLAZING IN WALLS, ENCLOSURES OR,
 BATHTUBS, SHOWERS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES MEASURED VERTICALLY
 ABOVE ANY STANDING OR WALKING SURFACE SHALL BE
 CONSIDERED A HAZARDOUS LOCATION. THIS SHALL APPLY TO
 SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING.
  
 12) NEITHER THE ELEVATION SHEETS NOR THE STRUCTURAL
 SHEETS PROVIDE THE WIND DESIGN CRITERIA NOR PRESSURES.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  