Plan Review Notes
Plan Review Notes For Permit 16070170
Permit Number 16070170
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-11 19:41:07REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - SINCE LIGHT NICHE IS OF CONDUCTIVE PROPERTIES A # 8
 AWG EQUIPMENT GROUNDING CONDUCTOR MUST BE ROUTED IN THE
 RACEWAY AND A LISTED COMPOUND MUST BE APPLIED TO THE
 FORMING SHELL LUG TERMINAL FOR THE BONDING CONNECTION
 PREVENTING DETERIORATING EFFECT OF POOL WATER. NEC
 680.23
  
 - ON THE ONE LINE DIAGRAM SPECIFY WHAT SIZE WIRE IS
 FEEDING THE POOL EQUIPMENT PANEL AND THE OVERCURRENT
 PROTECTION SIZE COMING FROM THE SERVICE PANEL. FBC 107,
 NEC 215.5