| 2016-07-21 09:59:48 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070154 |
| | ADD: 1010 9TH ST. |
| | CONT: ALL CONSTRUCTION SYSTEMS, INC. |
| | TEL: 305-319-2499 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES PLUMBING DAMAGES |
| | AND WATER REPAIRS. SHEET A-02 INDICATES WATER DAMAGE IN |
| | THE APT. # 6 THAT COMPROMISED CEILINGS AND SOME WALLS |
| | IN APT. 1, 2 & 3. THE PLANS DO NOT PROVIDE UNDER WHAT |
| | CODE THEY WERE DEVELOPED NOR IF USING THE WORK AREA |
| | METHOD WHAT LEVEL OF ALTERATION THIS IS GOING TO BE. |
| | BUILT IN 1962/ 2 STORY/ CBS. |
| | 2014 FBC-EXISTING BUILDING CODE 301.1 THE REPAIR, |
| | ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION |
| | OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | METHODS LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS |
| | SELECTED BY THE APPLICANT. APPLICATION OF A METHOD |
| | SHALL BE THE SOLE BASIS FOR ASSESSING THE COMPLIANCE OF |
| | WORK PERFORMED UNDER A SINGLE PERMIT UNLESS OTHERWISE |
| | APPROVED BY THE CODE OFFICIAL. SECTIONS 301.1.1 THROUGH |
| | 301.1.3 SHALL NOT BE APPLIED IN COMBINATION WITH EACH |
| | OTHER. |
| | |
| | 1A) THE PLANS INDICATE WITH NOTE ON THE PLANS THE |
| | REPLACEMENT OF DRYWALL CEILINGS. PLEASE NOTE UNTIL THE |
| | METHOD OF CODE COMPLIANCE LISTED ABOVE, THE FIRE RATING |
| | OF THE FLOOR SYSTEM CAN NOT BE IDENTIFIED. UNDER THE |
| | CURRENT CODE THE 2014 FBC-B 707.3.10 REQUIRES 2 HOUR |
| | SEPARATION OF FIRE AREAS IN HORIZONTAL ASSEMBLIES ( THE |
| | 2ND FLOOR ASSEMBLY) WHERE AS UNDER THE CODE THE |
| | BUILDING WAS BUILT 1960-1961 ADDENDUM TO THE 1957-1958 |
| | SOUTHERN STANDARD BUILDING CODE ADOPTED BY WEST PALM |
| | BEACH ONLY REQUIRES A 1 HOUR FIRE RATING. |
| | |
| | 1B) THERE IS ANOTHER NOTE INDICATING THE REPLACEMENT OF |
| | DRYWALL IN THE PARTITIONS BETWEEN UNITS. THE DETAIL FOR |
| | THE 1 HOUR FIRE RATED ASSEMBLY PLEASE PROVIDE EITHER A |
| | UL WALL ASSEMBLY OR GYPSOM ASSOCIATION ASSEMBLY. |
| | |
| | 1C) THE 1 HOUR WALL DETAIL INDICATES THIS IS A CUT |
| | SECTION THROUGH APARTMENT 4 & 5, IS THERE WORK BEING |
| | COMPLETED ON THIS TENANT SEPARATION WALL. |
| | 107.2.1.3 |
| | |
| | 2) PLEASE REVIEW THE REQUIREMENTS FOR FLOOR INSULATION |
| | IN THE 2ND FLOOR ASSEMBLY. FOR TILE, STONE, MARBLE AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A UNKNOWN FLOOR TRUSS SYSTEM OR |
| | DIMENSION 2X FRAMING MEMBERS. |
| | |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |