Plan Review Notes
Plan Review Notes For Permit 16070096
Permit Number 16070096
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-20 06:39:451) A MINIMUM FOUR FEET HIGH FENCE SHALL SURROUND THE
 EQUIPMENT AREA PER 2014 FBC SEC. 454.1.5.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 MAIN DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMPS
 INCLUDING THE PUMP CURVE. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SUBMIT SPECIFICATIONS FOR THE CHLORINE FEEDER, PH
 FEEDER, & SALT CHLORINATOR. WPB AMEND. TO FBC SEC.
 107.2.1.
 5) THE PLANS REFER TO A POOL HEATER. SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE POOL HEATER. THE
 HEATER SHALL COMPLY WITH 2014 FBC-ENERGY SEC. C404.7.
 6) SHT. 3 CALLS OUT 6 INCH MAIN DRAINS BUT SHT. 4 SHOWS
 ONE OF THE MAIN DRAINS AS 4 INCH. CLARIFY.
 7) SHOW COMPLIANCE WITH 2014 FBC SEC.454.1.6.5.7.
 PROPORTIONING VALVES ARE REQUIRED ON RETURN, MAIN DRAIN
 AND SURFACE OVERFLOW LINES.
 8) SHT. 3 OF 7 LISTS THE WIDTH OF THE POOL AS 26 FEET,
 8 INCHES BUT SHT. 2 OF 7 HAS A MEASUREMENT OF 35 FEET,
 8 INCHES. I COULD NOT FIND THE 26 FEET, 8 INCH
 DIMENSION ON THE PLAN. CLARIFY
 REVIEW NOT COMPLETE.
 9) IF THE POOL IS GREATER THAN 30 FEET WIDE, THE POOL
 SHALL HAVE EITHER FLOOR INLETS ONLY OR A COMBINATION OF
 FLOOR AND WALL INLETS PER 2014 FBC SEC.454.1.6.5.9.4.
 10) IF A POOL HEATER IS BEING INSTALLED, A TIME SWITCH
 OR OTHER METHOD THAT CAN AUTOMATICALLY TURN OFF AND ON
 HEATERS COMPLYING WITH 2014 FBC-ENERGY SEC.C404.7.2
 SHALL BE INSTALLED.
 11) HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH COVERS
 COMPLYING WITH 2014 FBC-ENERGY SEC.C404.7.3.
 12) THE FILTRATION SYSTEM FOR SWIMMING POOLS SHALL BE
 CAPABLE OF MEETING ALL OTHER REQUIREMENTS OF THESE
 RULES WHILE PROVIDING A FLOW RATE OF AT LEAST 0.75 GPM
 FOR EACH LIVING UNIT AT NONTRANSIENT UNIT. CONFIRM
 COMPLIANCE. 2014 FBC SEC.454.1.1.1.
 13) THE POOL WATER SHALL NOT DRAIN TO THE SANITARY OR
 STORM DRAINAGE SYSTEM PER CITY ORDINANCE SEC. 90-126 (
 B ) ( 5 ) & 90-203, 90-205.
 14) POOLS EQUIPPED WITH HEATERS SHALL HAVE A FIXED
 THERMOMETER MOUNTED IN THE POOL RECIRCULATION LINE
 DOWNSTREAM FROM THE HEATER OUTLET PER 2014 FBC
 SEC.454.1.6.5.14.
 15) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES
 WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FRROM
 THE SYSTEM SHALL BE PROVIDED. 2014 FBC
 SEC.454.1.6.5.14.
 16) ALL CHEMICALS SHALL BE FED INTO THE RETURN LINE
 AFTER THE PUMP, HEATER AND FILTERS IN ACCORDANCE WITH
 2014 FBC SEC.454.1.6.5.16.
 17) A ROOM OR SPACE SHALL BE PROVIDED FOR CHEMICALS TO
 BE STORED IN ACCORDANCE WITH 2014 FBC SEC. 454.1.3.3.4.
 18) VAK PAK SHEET ( 5 OF 7) REFERS TO AP 16C. WHAT IS
 THIS? I COULD NOT FIND ANY INFORMATION ON THIS ON THE
 VAK PAK WEBSITE. CLARIFY/SUBMIT SPECIFICATIONS.
 19) THE AUTOFILL FOR THE COLLECTOR TANK SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTION DEVICE. 2014 FBC
 SEC. 454.1.6.3.
 20) SHT. 3 OF 7 SHOWS THE BATHING LOAD AS 23 PERSONS
 AND SHT. A-1.00 SHOWS THE POOL OCCUPANT LOAD AS 35.
 CLARIFY.ALSO THE AREA OF THE POOL IS SHOWN AS 1737 SQ.
 FT. ON A-1.00 AND SHT.3 OF 7 SHOWS 1397 SQ. FT.
 CLARIFY.
 21) INDICATE THE TERMINATION POINT OF THE FLOOR DRAIN
 IN THE VAK PAK ENCLOSURE. A TRAP PRIMER WILL BE
 REQUIRED IF CONNECTED TO THE SANITARY SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  