| 2016-07-20 06:39:45 | 1) A MINIMUM FOUR FEET HIGH FENCE SHALL SURROUND THE |
| | EQUIPMENT AREA PER 2014 FBC SEC. 454.1.5.1. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | MAIN DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMPS |
| | INCLUDING THE PUMP CURVE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 4) SUBMIT SPECIFICATIONS FOR THE CHLORINE FEEDER, PH |
| | FEEDER, & SALT CHLORINATOR. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 5) THE PLANS REFER TO A POOL HEATER. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR THE POOL HEATER. THE |
| | HEATER SHALL COMPLY WITH 2014 FBC-ENERGY SEC. C404.7. |
| | 6) SHT. 3 CALLS OUT 6 INCH MAIN DRAINS BUT SHT. 4 SHOWS |
| | ONE OF THE MAIN DRAINS AS 4 INCH. CLARIFY. |
| | 7) SHOW COMPLIANCE WITH 2014 FBC SEC.454.1.6.5.7. |
| | PROPORTIONING VALVES ARE REQUIRED ON RETURN, MAIN DRAIN |
| | AND SURFACE OVERFLOW LINES. |
| | 8) SHT. 3 OF 7 LISTS THE WIDTH OF THE POOL AS 26 FEET, |
| | 8 INCHES BUT SHT. 2 OF 7 HAS A MEASUREMENT OF 35 FEET, |
| | 8 INCHES. I COULD NOT FIND THE 26 FEET, 8 INCH |
| | DIMENSION ON THE PLAN. CLARIFY |
| | REVIEW NOT COMPLETE. |
| | 9) IF THE POOL IS GREATER THAN 30 FEET WIDE, THE POOL |
| | SHALL HAVE EITHER FLOOR INLETS ONLY OR A COMBINATION OF |
| | FLOOR AND WALL INLETS PER 2014 FBC SEC.454.1.6.5.9.4. |
| | 10) IF A POOL HEATER IS BEING INSTALLED, A TIME SWITCH |
| | OR OTHER METHOD THAT CAN AUTOMATICALLY TURN OFF AND ON |
| | HEATERS COMPLYING WITH 2014 FBC-ENERGY SEC.C404.7.2 |
| | SHALL BE INSTALLED. |
| | 11) HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH COVERS |
| | COMPLYING WITH 2014 FBC-ENERGY SEC.C404.7.3. |
| | 12) THE FILTRATION SYSTEM FOR SWIMMING POOLS SHALL BE |
| | CAPABLE OF MEETING ALL OTHER REQUIREMENTS OF THESE |
| | RULES WHILE PROVIDING A FLOW RATE OF AT LEAST 0.75 GPM |
| | FOR EACH LIVING UNIT AT NONTRANSIENT UNIT. CONFIRM |
| | COMPLIANCE. 2014 FBC SEC.454.1.1.1. |
| | 13) THE POOL WATER SHALL NOT DRAIN TO THE SANITARY OR |
| | STORM DRAINAGE SYSTEM PER CITY ORDINANCE SEC. 90-126 ( |
| | B ) ( 5 ) & 90-203, 90-205. |
| | 14) POOLS EQUIPPED WITH HEATERS SHALL HAVE A FIXED |
| | THERMOMETER MOUNTED IN THE POOL RECIRCULATION LINE |
| | DOWNSTREAM FROM THE HEATER OUTLET PER 2014 FBC |
| | SEC.454.1.6.5.14. |
| | 15) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES |
| | WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FRROM |
| | THE SYSTEM SHALL BE PROVIDED. 2014 FBC |
| | SEC.454.1.6.5.14. |
| | 16) ALL CHEMICALS SHALL BE FED INTO THE RETURN LINE |
| | AFTER THE PUMP, HEATER AND FILTERS IN ACCORDANCE WITH |
| | 2014 FBC SEC.454.1.6.5.16. |
| | 17) A ROOM OR SPACE SHALL BE PROVIDED FOR CHEMICALS TO |
| | BE STORED IN ACCORDANCE WITH 2014 FBC SEC. 454.1.3.3.4. |
| | 18) VAK PAK SHEET ( 5 OF 7) REFERS TO AP 16C. WHAT IS |
| | THIS? I COULD NOT FIND ANY INFORMATION ON THIS ON THE |
| | VAK PAK WEBSITE. CLARIFY/SUBMIT SPECIFICATIONS. |
| | 19) THE AUTOFILL FOR THE COLLECTOR TANK SHALL BE |
| | EQUIPPED WITH A BACKFLOW PREVENTION DEVICE. 2014 FBC |
| | SEC. 454.1.6.3. |
| | 20) SHT. 3 OF 7 SHOWS THE BATHING LOAD AS 23 PERSONS |
| | AND SHT. A-1.00 SHOWS THE POOL OCCUPANT LOAD AS 35. |
| | CLARIFY.ALSO THE AREA OF THE POOL IS SHOWN AS 1737 SQ. |
| | FT. ON A-1.00 AND SHT.3 OF 7 SHOWS 1397 SQ. FT. |
| | CLARIFY. |
| | 21) INDICATE THE TERMINATION POINT OF THE FLOOR DRAIN |
| | IN THE VAK PAK ENCLOSURE. A TRAP PRIMER WILL BE |
| | REQUIRED IF CONNECTED TO THE SANITARY SYSTEM. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |