Plan Review Notes
Plan Review Notes For Permit 16070096
Permit Number 16070096
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-21 10:41:48JOB PERMIT NUMBER: 16070096
 JOB ADDRESS: 838 ADAMS STREET
 WEST PALM BEACH FLORIDA
 DATE: JULY 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - PROVIDE MANUFACTURE SPECS ON ALL ASSOCIATED POOL
 EQUIPMENT SUCH AS HEATERS, POOL LIGHTS, CHLORINATOR,
 MOTOR PUMPS, AND ETC. FBC 107 MINIMUM PLAN REVIEW
 - IN ADDITION TO BONDING THE LIGHT NICHE TO THE
 EQUIPOTENTIAL GRID A # 8 AWG ?INSULATED? EQUIPMENT
 GROUNDING CONDUCTOR SHALL BE RAN INSIDE THE PVC CONDUIT
 EXTENDING DIRECTLY FROM THE FORMING SHELL AND A LISTED
 COMPOUND SHALL BE PLACED ON THE BONDING CONNECTION FOR
 ANY DETERIORATING EFFECT. NEC 680.23(2)(B)
 - IF POOL HEATERS ARE BEING INSTALLED PLEASE MODIFY ONE
 LINE DIAGRAM AND PANEL SCHEDULE IN ADDITION A TIME
 SWITCH CONTROL DEVICE SHALL BE INSTALLED PER FBC E
 SECTION C404.7.2
 - ADD A NOTE REFERENCING BONDING OF POOL WATER NEC
 680.26(C). IF A SEPARATE DEVICE IS BEING INSTALLED A
 MINIMUM OF 9?? SQUARED SURFACE AREA MUST BE COVERED BY
 POOL WATER.
 - SITE LIGHTING SHALL BE UNDER A SEPARATE PERMIT,
 INCLUDE EXTERIOR LIGHTING CONTROLS, PHOTOMETRICS ( FOOT
 CANDLE ILLUMINATION ), WIRE & BREAKER SIZE AND POWER
 SOURCE DIAGRAM.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  