Plan Review Notes
Plan Review Notes For Permit 16070096
Permit Number 16070096
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-05 10:54:17BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070096
 ADD: 838 ADAMS ST.
 CONT: LAGASSE POOL CONSTRUCTION
 TEL: 954-587-1000
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. AUGUST 05/2016
 ACTION: DENIED
  
 1) SHEET 2 OF 7 THE LEFT SIDE OF THE SHEET, INFORMATION
 HAS BEEN CUT OFF. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET 3 OF 7 INDICATES THE AREA OF THE POOL TO BE
 1397 SQ. FT./ WHEREAS SHEET A-1.00 SHOWS A SQ. FOOTAGE
 OF 1737 SQ. FT. DISCREPANCY IN PLANS 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 3) SHEET A-1.00 FOR THE OCCUPANT LOAD OF THE POOL DECK
 IS 3387 SQ. FT. /30 = 113 OCCUPANTS. PLEASE REVIEW THE
 2014 FBC-B TABLE 1004.1.2 POOL DECKS ARE TAKEN AT 15
 SQ. FT. 3387/15 = 226 OCCUPANTS.
  
 4) SHEET 5 OF 7 SCHEMATIC PLAN WITH NOTES L & M LINES
 TO AND FROM HEATER. PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE POOL HEATER. THE HEATER SHALL
 COMPLY WITH THE 2014 FBC-ENERGY CODE C404.7.
  
 5) PLEASE PROVIDE WHERE COMPLIANCE WITH THE 2014
 FBC-ENERGY CODE C404.7.2 A TIME CLOCK OR OTHER METHOD
 THAT WILL AUTOMATICALLY TURN OFF AND ON THE HEATER.
  
 6) PLEASE ALSO SHOW COMPLIANCE WITH THE 2014 FBC-ENERGY
 CODE HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  