| Plan Review Notes For Permit 16070093 |
| Permit Number |
16070093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-13 19:36:14 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - NEC 600.5 SIGN SHALL BE ON A DEDICATED 20 AMP BRANCH | | | CIRCUIT IF EXISTING MARK ON PLANS. | | | | | | - NEC 600.6 PROVIDE A DISCONNECT WITHIN SIGHT OF THE | | | SIGN. THIS APPLIES FOR BOTH NORTH AND SOUTH SIDE ! | | | | | | - ALL GROUNDING AND BONDING SHALL BE IN ACCORDANCE WITH | | | NEC 600.7. ( GENERAL COMMENT ) | | | | | | - C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. | | 2016-07-13 10:53:13 | SENT TO ZONING FOR REVIEW |
|