2016-07-13 19:36:14REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - NEC 600.5 SIGN SHALL BE ON A DEDICATED 20 AMP BRANCH
 CIRCUIT IF EXISTING MARK ON PLANS.
  
 - NEC 600.6 PROVIDE A DISCONNECT WITHIN SIGHT OF THE
 SIGN. THIS APPLIES FOR BOTH NORTH AND SOUTH SIDE !
  
 - ALL GROUNDING AND BONDING SHALL BE IN ACCORDANCE WITH
 NEC 600.7. ( GENERAL COMMENT )
  
 - C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
2016-07-13 10:53:13SENT TO ZONING FOR REVIEW