| Plan Review Notes For Permit 16070084 |
| Permit Number |
16070084 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-30 06:50:37 | 1) SUBMIT THE SPECIFIC SHEETS THAT ARE APPLICABLE ONLY | | | FOR THE WORK TO BE DONE FOR THE FOUNDATION ONLY PERMIT. | | | THERE ARE IRRIGATION AND LANDSCAPING PLANS, PROPANE GAS | | | PLANS, STORM DRAINAGE, ETC. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 2) IF ANY PIPING FOR THE PLUMBING SYSTEM WILL BE | | | INSTALLED UNDER THIS PERMIT, SUBMIT RISER DIAGRAMS FOR | | | THE WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. | | | 3) IF THE INTERCEPTORS / SEPARATORS ARE BEING INSTALLED | | | UNDER THIS PERMIT, SUBMIT SIZING CALCULATIONS FOR EACH | | | INTERCEPTOR. THE SIZE, TYPE AND LOCATION OF EACH | | | INTERCEPTOR AND EACH SEPARATOR SHALL BE APPROVED BY THE | | | PLUMBING OFFICIAL PER 2014 FBC-PLUMBING SEC.1003.2. | | | 4) A SAMPLING PORT IS REQUIRED IN THE DISCHARGE LINE OF | | | EACH INTERCEPTOR IN ACCORDANCE WITH CITY ORDINANCE. | | | 5) THE OIL / SAND SEPARATOR SHALL COMPLY WITH 2014 | | | FBC-PLUMBING SECS. 1003.4.2. | | | | | | NOTE: A COMPREHENSIVE PLUMBING PLAN REVIEW COULD NOT BE | | | PERFORMED AT THIS TIME AS THE SCOPE OF WORK TO BE DONE | | | IS NOT CLEARLY DEFINED ON THE PLANS. ONCE THIS IS | | | CLARIFIED, ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | FORTHCCOMING ON THE RE-REVIEW. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | . |
|