| Date |
Text |
| 2016-07-18 16:43:25 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | THIS APPROVAL IS ONLY FOR THE FOUNDATION. |
| | |
| | |
| | |
| | 1) SHEET COV - THERE IS NO REFERNECE TO ANY FIRE CODE |
| | COMPLIANCE. |
| | |
| | AT MINIMUM PLEASE ENSURE COMPLIANCE WITH THE BELOW |
| | NOTED CODES: |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | UNDERGROUND FIRE LINE WORK SHALL COMPLY WITH NFPA 24, |
| | STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE |
| | MAINS AND THEIR APPURTENANCES, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | |
| | |
| | 2) SHEET COV - THERE IS NO INDICATION OF A FIRE |
| | SPRINKLER SYSTEM. PER NFPA 1, CHAPTER 13, FIRE |
| | PROTECTION SYSTEMS. |
| | 13.3.2.3 NEW BUILDINGS HOUSING EMERGENCY FIRE, RESCUE, |
| | OR AMBULANCE SERVICES SHALL BE PROTECTED THROUGHOUT BY |
| | APPROVED AUTOMATIC SPRINKLER SYSTEMS. |
| | |
| | SHOULD ANY WORK RELATED TO THE FIRE SPRINKLER SYSTEM |
| | INVOLVE UNDERGROUND WORK PLEASE PROVIDED THE |
| | APPROPRIATE REVISION OR AS-BUILT. |
| | |
| | |
| | 3) SHEET COV - WHERE A FIRE PROTECTION ENGINEERED |
| | SYSTEM IS PROPOSED, PER FLORIDA ADMINISTRATIVE CODE |
| | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | PLEASE PROVIDE AT MINIMUM A SEALED LETTER FROM A |
| | QUAILIFED ENGINEER OF RECORD INDICATING THE NOTED |
| | INFORMATION ABOVE FOR THE PROJECT. |
| | |
| | |
| | 4) ALL UNDERGROUND FIRE LINES SHALL BE SUBMITTED, |
| | CONSTURCTED AND INSPECTED PER NFPA 24. |
| | |
| | PLEASE ENSURE ALL UNDERGROUND FIRE LINES COMPLY WITH |
| | THE ABOVE AND INSPECTED BY FIRE AND MECHANICAL PER THE |
| | CODE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | ALL OTHER COMMENTS ARE NOTED AS INFORMATIONAL FOR THE |
| | BUILDING PLAN SUBMITTAL: |
| | |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 |
| | EDITION. |
| | |
| | |
| | 1) SHEET 101 A - A NOTE IS INDICATED " RANGE HOOD SEE |
| | MECHANICAL DRAWINGS FOR DETAIL" NO MECHANICAL SHEET IS |
| | INCLUDED IN PLAN SUBMITTAL. |
| | |
| | PROVIDE APPLICABLE MECHANICAL SHEET. |
| | |
| | 2) NO SHEETS - NO MECHANCIAL SHEETS ARE INCLUDED IN |
| | PLAN SUBMITTAL |
| | |
| | PROVIDE ALL MECHANICAL SHEETS. |
| | |
| | 3) NO SHEET - NO REFERENCE IS INDICATED FOR FIRE |
| | PROTECTION OF THE HOOD SYSTEM. PER NFPA 101, CHAPTER 9 |
| | BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT |
| | 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING |
| | EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD |
| | FOR VENTILATION CONTROL AND FIRE PROTECTION OF |
| | COMMERCIAL COOKING OPERATIONS, UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE. |
| | NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 GENERAL. |
| | 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING |
| | SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN |
| | EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND |
| | PERFORMANCE REQUIREMENTS OF THIS STANDARD. |
| | 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN |
| | VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE |
| | IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE |
| | PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT. |
| | |
| | PLEASE PROVIDE AT NOTE AND MINIMUM INDICATING, ALL |
| | KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH NFPA |
| | 96, STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS. |
| | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS |
| | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. |
| | |
| | |
| | 4) SHEET A 410 - PER FLORIDA 69A-60.0081; NOTICE |
| | SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE A NOTE AT MINIMUM INDICATING THE ABOVE. |
| | |
| | 5) A SHEETS - THERE IS NO DOOR SCHEDULE INCLUDED IN THE |
| | PLAN SUBMITTAL. |
| | |
| | PLEASE PROVIDE THE APPLICABLE DOOR SCHEDULE INCLUDING |
| | ALL APPLICABLE EXIT HARDWARE AND FIRE RATINGS. |
| | |
| | |
| | 6) SHEET A 100 - A GENERATOR AND FUEL TANKS NOTE IS |
| | INDICATED, WHAT IS THE FUEL SOURCE OF THE GENERATOR? |
| | THE GENERATOR AND FUEL SOURCE TANKS SHALL BE UNDER |
| | SEPARATE SHOP DRAWINGS AND PERMITS. |
| | |
| | PLEASE PROVIDE A NOTE FOR COMPLIANCE WITH NFPA 110, |
| | STANDARD FOR EMEGENCY AND STANDBY POWER SYSTEMS AND |
| | NFPA 54, NATIONAL FUEL GAS CODE. |
| | |
| | |
| | |
| | 7) SHEET A 411 - THERE IS NO HANDRAIL AND/OR GAURDRAIL |
| | DETAIL FOR THE STAIRS. |
| | |
| | PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101, |
| | CHAPTER 7, 7.2.2.4.4 HANDRAIL DETAILS; |
| | 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL NOT BE LESS |
| | THAN 34 IN. AND NOT MORE THAN 38 IN. ABOVE THE SURFACE |
| | OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE |
| | RAIL FROM THE LEADING EDGE OF THE TREAD. |
| | |
| | 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD |
| | REQUIREMENTS. |
| | 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8 |
| | SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD |
| | FROM THE SURFACE ADJACENT THERETO. |
| | 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065 |
| | MM) HIGH |
| | |
| | |
| | |
| | 8) SHEET A 411 - THERE IS NO HANDRAIL GAURDRAIL FOR THE |
| | RAMP. |
| | |
| | PLEASE PROVIDE DETAIL IN COMPLIANCE WITH NFPA 101, |
| | CHAPTER 7, 7.2.5.4 GUARDS AND HANDRAILS. 7.2.5.4.1 |
| | GUARDS COMPLYING WITH 7.2.2.4 SHALL BE PROVIDED FOR |
| | RAMPS, UNLESS OTHERWISE PROVIDED IN 7.2.5.4.4. |
| | 7.2.5.4.2 HANDRAILS COMPLYING WITH 7.2.2.4 SHALL BE |
| | PROVIDED ALONG BOTH SIDES OF A RAMP RUN WITH A RISE |
| | GREATER THAN 6 IN. (150 MM), UNLESS OTHERWISE PROVIDED |
| | IN 7.2.5.4.4. |
| | 7.2.5.4.3 THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE |
| | MEASURED VERTICALLY TO THE TOP OF THE GUARD OR RAIL |
| | FROM THE WALKING SURFACE ADJACENT THERETO. |
| | |
| | |
| | |
| | 9) SHEET E 31 - THERE IS NO INDICATION OF EXIT STAIR |
| | LIGHTING. 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 7.8.1 GENERAL. |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| | PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| | |
| | |
| | 10) SHEET E 31 - THERE IS NO INDICATIONS OF THE KITCHEN |
| | EQUIPMENT PLAN. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 11) FA 2.1 - THERE IS NO 2ND FLOOR FA PALN. |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | 12) SHEET 101 A - A GWH IS INDICATED WITH NO DETAILS. |
| | |
| | LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER |
| | SEPARATE SHOP DRAWINGS. |
| | |
| | |
| | 13) IS LP/NG GAS PROPOSED FOR THE STOVE/OVEN? NO DETAIL |
| | IS PROVIDED. |
| | |
| | LP/NG GAS PIPING AND DETAIL SHALL BE SUBMITTED UNDER |
| | SEPARATE SHOP DRAWINGS. |
| | |
| | |
| | |
| | 14) FIREMAN POLES ARE INDICATED; HOWEVER, THERE IS NO |
| | DETAIL, I.E. HOLE SIZE, SAFETY EQUIPMENT, POLE TYPE, |
| | ETC. |
| | |
| | PLEASE PROVIDE DETAIL. |
| | |
| | |
| | |
| | 15) A KNOX BOX IS REQUIRED FOR THIS STRUCTURE LOCATED |
| | IN COORDINATION WITH THE AHJ. |
| | |
| | PLEASE PROVIDE A NOTE. |
| | |
| | |
| | |
| | 16) HOW IS CONTROLLED GATE ACCESS PROVIDED? A KNOX KEY |
| | SWITCH FOR ENTRY IS RECOMMENDED BUT SHALL BE |
| | COORDINATED WITH THE AHJ? |
| | |
| | PLEASE PROVIDE A NOTE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |