| 2016-07-20 11:58:44 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: WEST PALM BEACH FIRE STATION #4 |
| | JOB ADDRESS: 1718 PARKER AVE. |
| | DESCRIPTION: FOUNDATION ONLY |
| | MAST. PERMIT: 16070084 |
| | REVISION: N/A |
| | |
| | THE SCOPE OF THIS REVISION IS LIMITED TO THAT INDICATED |
| | ABOVE AND ON THE PERMIT APPLICATION, (FOUNDATION ONLY). |
| | THE SUBMITTED PLAN SET DOES NOT INCLUDE THE SITE AND OR |
| | RISER DIAGRAM. YOU SHALL SUBMIT A SITE PLAN INDICATING |
| | THE LOCATION OF THE UTILITY TRANSFORMER SERVICE THE |
| | PREMISES AND THE LOCATION OF THE METER AND MAIN |
| | DISCONNECTS. FURTHERMORE YOU SHALL INCLUDE AN |
| | ELECTRICAL RISER DIAGRAM WITH LOAD CALCS FOR THE |
| | PROPOSED STRUCTURE TO DETERMINE PROPER GROUNDING |
| | ELECTRODE CONDUCTOR SIZING. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |