| Plan Review Notes For Permit 16070073 |
| Permit Number |
16070073 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-18 17:05:59 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | MAKE CORRECTIONS TO DUCT SIZES AND CFM QUANTITIES AS | | | PER THE HEAT LOAD CALCULATIONS SUBMITTED. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | R403.6.1.1 COOLING EQUIPMENT CAPACITY. COOLING ONLY | | | EQUIPMENT SHALL BE SELECTED SO THAT ITS TOTAL CAPACITY | | | IS NOT LESS THAN THE CALCULATED TOTAL LOAD, BUT NOT | | | MORE THAN 1.15 TIMES GREATER THAN THE TOTAL LOAD | | | CALCULATED ACCORDING TO THE PROCEDURE SELECTED IN | | | SECTION 403.6, OR THE CLOSEST AVAILABLE SIZE PROVIDED | | | BY THE MANUFACTURER?S PRODUCT LINES. THE CORRESPONDING | | | LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE LESS THAN | | | THE CALCULATED LATENT LOAD. | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | | | | | | | |
|