Plan Review Notes For Permit 16070073
Permit Number 16070073
Review Stop I
Sequence Number 1
Notes
Date Text
2016-11-21 17:28:54SPOKE TO HOMEOWNER ON 11/21/2016. I EXPLAINED AS PER
 THE SUBMITTED HEAT LOAD CALCULATION, THE TOTAL BTUH FOR
 LEVEL 1 IS 27415 AND AS PER ENERGY CALCULATIONS 36,000
 BTU -16 SEER. THE SUBMITTED HEAT LOAD CALCULATION TOTAL
 BTUH FOR LEVEL 2 IS 27461 AND AS PER ENERGY
 CALCULATIONS 36,000 BTU -16 SEER. HEAT LOADS AND ENERGY
 CALCULATIONS NEED TO BE REVISED TO MEET INSTALLATION OR
 INSTALLATION HAS TO CONFORM TO SUBMITTED DOCUMENT.
 JORGE V. 11/21/2016.