| Plan Review Notes For Permit 16070073 |
| Permit Number |
16070073 |
|
| Review Stop |
I |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-21 17:28:54 | SPOKE TO HOMEOWNER ON 11/21/2016. I EXPLAINED AS PER | | | THE SUBMITTED HEAT LOAD CALCULATION, THE TOTAL BTUH FOR | | | LEVEL 1 IS 27415 AND AS PER ENERGY CALCULATIONS 36,000 | | | BTU -16 SEER. THE SUBMITTED HEAT LOAD CALCULATION TOTAL | | | BTUH FOR LEVEL 2 IS 27461 AND AS PER ENERGY | | | CALCULATIONS 36,000 BTU -16 SEER. HEAT LOADS AND ENERGY | | | CALCULATIONS NEED TO BE REVISED TO MEET INSTALLATION OR | | | INSTALLATION HAS TO CONFORM TO SUBMITTED DOCUMENT. | | | JORGE V. 11/21/2016. | | 2016-07-06 10:19:42 | TLARGE'S DESK |
|