Plan Review Notes
Plan Review Notes For Permit 16070062
Permit Number 16070062
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-07 15:03:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - CLARIFY HOW A 60 AMP SUB PANEL IS BEING FED FROM THE
 EXISTING SERVICE WITH # 10 AWG IS GONA BE SUFFICIENT
 FOR A 3000 VA POOL PUMP AND A 10000 VA POOL HEATER ?
 REFLECT EXISTING SERVICE RISER DIAGRAM TO VERIFY LOAD
 DISTRUBUTION NEC 215.5
  
 - CORRECT LOAD CALCULATION IN ACCORDANCE WITH NEC
 220.82/83 OPTIONAL METHOD IF THAT IS THE INTENT AND
 TAKE A LOOK AT THE AC DEMANDS.
  
 - PROVIDE A # 8 AWG EQUIPMENT GROUNDING CONDUCTOR
 INSIDE THE RACEWAY FOR THE LIGHT NICHE BONDING.
 ENCAPSULATE THE FORMING SHELL LUG TERMINAL WITH A
 LISTED COMPOUND FOR DETERIORATION OF CONNECTION. NEC
 680.23(B)(1)(2)
  
 - SHOW BONDING DETAIL FOR SHED IF REQUIRED PER NEC
 680.26(7) FIXED METAL PARTS WITHIN 5'