| 2016-10-18 19:25:57 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 335 KENILWORTH BLVD. |
| | DESCRIPTION: INTERIOR REPAIRS TO INCLUDE NEW ELECTRICAL |
| | AND HVAC |
| | MASTER PERMIT: 16070049 |
| | |
| | THIS WAS REVIEWED ONCE BEFORE. THE BELOW COMMENTS ARE |
| | NUMBERED IN ACCORDANCE WITH THE PREVIOUS COMMENTS. ANY |
| | GREATER NUMBER REPRESENTS NEW OBSERVATIONS. ADDITIONAL |
| | CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF SUBMITTED |
| | CORRECTIONS. |
| | 1. RESPONSE ACCEPTED |
| | 2. RESPONSE ACCEPTED |
| | 3. YOU SHALL CORRECTLY LABEL ALL PANELS ON THE RISER |
| | DIAGRAM TO MATCH THE PANEL SCHEDULES AND UNIT NUMBERS. |
| | YOU SHALL CORRECT THE LOAD CALCS AND OCPD FOR EACH UNIT |
| | AND MULTI DWELLING SERVICE INCLUDING THE LAUNDRY |
| | CIRCUIT LOADS. KEEP IN MIND THAT THE WATER HEATERS, |
| | RANGE, LIGHTING AND HVAC ARE CONTINUOUS LOADS. YOU |
| | SHALL INCLUDE CONDUCTOR SIZING AND PROPOSED INSULATION |
| | TYPE. THE GROUNDING SHALL COMPLY WITH NEC 250.53. BLDG. |
| | A RISER IS MISSING THE INTER-SYSTEM BONDING REQUIRED BY |
| | NEC 250.94. |
| | 4. ADDITIONAL CO (CARBON MONOXIDE) DETECTORS ARE |
| | REQUIRED FOR BEDROOMS 1 OF BLDG. A. |
| | 5. FBC-ER3905.8: A BLOCK NOTE STATING COMPLIANCE WITH |
| | THIS SHALL BE PLACED ON THE DRAWINGS. |
| | 6. RESPONSE ACCEPTED |
| | 7. FBC-ER3903.4: YOU INDICATE THAT THERE IS NO ATTIC, |
| | YET THE DRAWINGS FOR BLDG. A SUGGEST OTHERWISE. MAY I |
| | SUGGEST THAT THIS BE SWITCHED OUTSIDE THE ATTIC AND |
| | CONTROLLED WITH A SWITCH THAT HAS A PILOT SO AS TO |
| | INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON. |
| | 7. RESPONSE ACCEPTED |
| | 8. RESPONSE ACCEPTED |
| | 9. RESPONSE ACCEPTED |
| | 10. RESPONSE ACCEPTED |
| | 11. PER FBC BLDG. "A" UNITS 1 & 2 BATHROOMS REQUIRE |
| | MECHANICAL VENTILATION WHENEVER THE ROOM IS OCCUPIED. |
| | THEREFORE THE EXHAUST FAN SHALL BE CONNECTED TO THE |
| | LIGHT TO COME ON SIMULTANEOUSLY. |
| | 12. APT. 2 KITCHEN IS MISSING THE REQUIRED OUTLETS. |
| | 13. RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS |
| | SHALL IN ADDITION TO HAVING AND IN-USE TYPE COVER, BE |
| | LISTED WEATHER-RESISTANT. A BLOCK NOTE TO THIS SHALL BE |
| | INCLUDED ON THE DRAWINGS. |
| | 14. FBC-RE3901.7: BLDG. "B" IS MISSING THE EXTERIOR |
| | OUTLET REQUIRED BY CODE. |
| | 15. FBC-ER3903.4: A LIGHT CONTROLLED BY A WALL SWITCH |
| | IS REQUIRED IN THE WATER HEATER CLOSET. |
| | 16. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY |
| | INSTALLED LIGHTING FIXTURES SHALL BE OF THE |
| | HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE |
| | FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |