| 2016-07-20 06:49:43 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070043 |
| | ADD: 3920 N. FLAGLER DR. SUITE # ? 203 VS. 301 |
| | CONT: BEEMS DESIGNER INC. |
| | TEL: 561-629-4149 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 20/2016 |
| | ACTION: DENIED |
| | |
| | 1) THERE SEEMS TO BE A DISCREPANCY IN THE JOBSITE |
| | LOCATION BOTH THE PERMIT APPLICATION AND THE PROPERTY |
| | APPRAISERS OFFICE LIST THE OWNERS JAMES & TRICIA WOOD |
| | OWNERS OF PROPERTY AT 3920 N FLAGLER DR. SUITE # 203 |
| | WHEREAS THE PLANS INDICATE THE WORK BEING COMPLETED AT |
| | 3920 N. FLAGLER SUITE # 301. |
| | THE PROPERTY APPRAISERS OFFICE INDICATES ANTHONY & |
| | PATICIA ORRICO OWN THIS PROPERTY. IF THE WOODS RECENTLY |
| | BOUGHT THIS PROPERTY PLEASE BRING IN YOUR CLOSING |
| | PAPERS SO THE LAND FILE CAN BE UPDATED IF NOT PLEASE |
| | CORRECT THE PLANS TO REFLECT THE CORRECT SUITE NUMBER. |
| | 107.2.1.3 DISCREPANCY IN THE UNIT BEING REMODELED. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. |
| | |
| | 2) THE OWNERS HAVE NOT SIGNED THE PERMIT APPLICATION; A |
| | HOLD WILL BE PUT ON THE PERMIT ISSUANCE UNTIL THE |
| | NOTARIZED OWNERS SIGNATURE IS ON THE PERMIT |
| | APPLICATION. 105.3.1. ACTION ON APPLICATION. |
| | |
| | 3) SHEET A.21 INDICATES NEW FLOORS IN THE MASTER |
| | BATHROOM TO BE TILE AND THE POWDER ROOM TO RECEIVE NEW |
| | WOOD FLOORS. PLANS DO NOT INDICATE IF THE POWDER ROOM |
| | FLOORING IS TO BE A 3/4 PLANK FLOORING OR IF A LAMINATE |
| | WOOD FLOORING. FOR TILE, STONE, MARBLE AND WOOD |
| | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| | STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| | DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) SHEET A3.1 INDICATES THROUGHOUT THE SUITE THE USE OF |
| | SOFFITS AND DROPPED CEILINGS. PLEASE NOTE THERE IS A |
| | DETAIL SHOWING THE USE OF METAL TRACK SYSTEM. THE PLANS |
| | DO NOT PROVIDE WHERE CEILING FRAMING IS TO BE ATTACHED |
| | TO THE CONCRETE DECK, THE TYPE OF ATTACHMENT, SPACING |
| | OF THE ATTACHMENT, AND PENETRATION INTO THE CONCRETE |
| | DECK. THE PLANS DO NOT HAVE ANY INFORMATION FOR THE |
| | DROPPED CEILING THROUGH OUT THE SUITE. TYPE OF FRAMING |
| | MATERIAL, SIZE AND SPACING OF THE FRAMING MATERIAL, |
| | SPACING FOR CEILING JOIST, IF STIF BACKS ARE REQUIRED |
| | FOR THE SPANS NOR THE THICKNESS OF THE FINISH CEILING |
| | MATERIAL AND TYPE OF FINISH CEILING MATERIAL. WILL ALSO |
| | NEED TO KNOW THE DEFLECTION LIMITATION OF THE FINISH |
| | CEILING MATERIAL. 2014 FBC-B TABLE 2506.2 STEEL STUDS, |
| | NON-LOAD BEARING ASTM C 645 , TABLE 2508.1 STEEL |
| | FRAMING FOR GYPSUM BOARD ASTM 745 & TABLE 1604.3 |
| | DEFLECTION LIMITATIONS. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |