| Plan Review Notes For Permit 16070033 |
| Permit Number |
16070033 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-11 12:34:25 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #16070033 | | | 7/11/16 | | | | | | 1) SHEET A-301: PLEASE IDENTIFY ALL ROOMS AND SPACES ON | | | THE PLANS. | | | | | | 2) A-301: REFER TO SECTION 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 3) A-301: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | EXISTING AC SYSTEM THAT INCLUDES THE COOLING, HEATING, | | | AND CFM CAPACITIES. | | | | | | 4) A-301: PROVIDE A RETURN AIR PLAN PER SECTION 601.5, | | | AND NOTE THAT THE CORRIDOR SHALL NOT BE USED TO CONVEY | | | RETURN AIR PER SECTION 601.2: PROVIDE A DUCTED RETURN | | | SYSTEM. | | | | | | 5) A-200: IDENTIFY THE NAME OF THE PROPOSED BUSINESS | | | AND OCCUPANCY CLASSIFICATION PER THE FBC-14. THE PLAN | | | INDICATES AN "OPERATION ROOM". PLEASE CLARIFY WHAT TYPE | | | OF "OPERATIONS"ARE TO BE PERFORMED THERE. PLEASE NOTE | | | THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER CORRECTED | | | PLANS ARE RESUBMITTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|