Plan Review Notes
Plan Review Notes For Permit 16070033
Permit Number 16070033
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-11 12:34:251ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16070033
 7/11/16
  
 1) SHEET A-301: PLEASE IDENTIFY ALL ROOMS AND SPACES ON
 THE PLANS.
  
 2) A-301: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) A-301: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 EXISTING AC SYSTEM THAT INCLUDES THE COOLING, HEATING,
 AND CFM CAPACITIES.
  
 4) A-301: PROVIDE A RETURN AIR PLAN PER SECTION 601.5,
 AND NOTE THAT THE CORRIDOR SHALL NOT BE USED TO CONVEY
 RETURN AIR PER SECTION 601.2: PROVIDE A DUCTED RETURN
 SYSTEM.
  
 5) A-200: IDENTIFY THE NAME OF THE PROPOSED BUSINESS
 AND OCCUPANCY CLASSIFICATION PER THE FBC-14. THE PLAN
 INDICATES AN "OPERATION ROOM". PLEASE CLARIFY WHAT TYPE
 OF "OPERATIONS"ARE TO BE PERFORMED THERE. PLEASE NOTE
 THAT ADDITIONAL COMMENTS MAY FOLLOW AFTER CORRECTED
 PLANS ARE RESUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved