2016-08-08 10:40:532ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070025
 8/8/16
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. I AM
 REPRINTING IT BELOW. PLEASE NOTE THAT THE ARCHITECT HAS
 SIGNED THE ENERGY CALCULATIONS BUT NOT THE AC
 CALCULATIONS.
 1) IN REGARD TO THE SUBMITTED AC CALCULATIONS PREPARED
 FOR THE PROJECT BY TOM PLATANIA- PRO CALCS LLC., PLEASE
 REFER TO SECTION 105.3.1.2(3) FBC-14 BUILDING:
 AN AIR-CONDITIONING SYSTEM MAY BE DESIGNED BY AN
 INSTALLING AIR-CONDITIONING CONTRACTOR CERTIFIED UNDER
 CHAPTER 489, FLORIDA STATUTES, TO SERVE ANY BUILDING OR
 ADDITION WHICH IS DESIGNED TO ACCOMMODATE FEWER THAN
 100 PERSONS AND REQUIRES AN AIR-CONDITIONING SYSTEM
 WITH A VALUE OF $125,000 OR LESS; AND WHEN A 15-TON-PER
 SYSTEM OR LESS IS DESIGNED FOR A SINGULAR SPACE OF A
 BUILDING AND EACH 15-TON SYSTEM OR LESS HAS AN
 INDEPENDENT DUCT SYSTEM. SYSTEMS NOT COMPLYING WITH THE
 ABOVE REQUIRE DESIGN DOCUMENTS THAT ARE TO BE SEALED BY
 A PROFESSIONAL ENGINEER.
 PLEASE CLARIFY IF MR. PLATANIA IS EITHER THE ENGINEER
 OF RECORD OR THE INSTALLING AC CONTRACTOR.
  
 2) THE AC LOAD CALCULATIONS AND THE EQUIPMENT SCHEDULE
 ON M.1 IDENTIFY THE NEW SYSTEMS AS AC-6 & AC-7, HOWEVER
 THEY ARE INCORRECTLY IDENTIFIED AS AHU-1 & AHU-2 IN THE
 ENERGY CALCULATIONS.
  
 3) M.1: PLEASE SHOW THE DUCT LAYOUTS FOR AHU-3 AND
 AHU-4. INDICATE DUCT SIZES AND WHICH DUCTS ARE NEW,
 EXISTING, OR RELOCATED.
  
 4) M.1: SHOW THE DISCHARGE LOCATION FOR THE CONDENSATE
 PIPE SERVING AHU-7.
  
 5) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW (COMMENT
 #12), PROVIDE A PRODUCT APPROVAL OR NOA FOR THE
 LOUVERS. WHAT HAS BEEN SUBMITTED IS A MANUFACTURER'S
 DATA SHEET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  