| 2016-08-11 07:54:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070025 |
| | ADD: 2450 METRO CENTRE BLVD. |
| | CONT: MEDICAL CONSULTANTS PLUS |
| | TEL: 954-444-3325 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. AUGUST 11/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 & LIFE SAFETY WILL REQUIRE RATED |
| | CORRIDORS. THE CORRIDOR IS A LOOPED SYSTEM. TAKING THE |
| | DIAGONAL OPPOSITE WHAT IS LAID OUT IN THE LIFE SAFETY |
| | SHEET WILL MAKE THE LONGEST TRAVEL DISTANCE TO AN EXIT, |
| | IN EACH CASE THE OCCUPANT LOAD WOULD BE OVER 30 |
| | OCCUPANTS SEE FBC-B TABLE 1018.1, BUSINESS OCCUPANCY |
| | WHEN THE CORRIDOR SERVES AN OCCUPANT LOAD GREATER THAN |
| | 30 IN A NON-SPRINKLERED BUILDING. |
| | |
| | 1A) FBC-B 1018.6 CORRIDOR CONTINUITY. |
| | FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS |
| | FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE |
| | INTERRUPTED BY INTERVENING ROOMS. WHERE THE PATH OF |
| | EGRESS TRAVEL WITHIN A FIRE-RESISTANCE-RATED CORRIDOR |
| | TO THE EXIT INCLUDES TRAVEL ALONG UNENCLOSED EXIT |
| | ACCESS STAIRWAYS OR RAMPS, THE FIRE RESISTANCE-RATING |
| | SHALL BE CONTINUOUS FOR THE LENGTH OF THE STAIRWAY OR |
| | RAMP AND FOR THE LENGTH OF THE CONNECTING CORRIDOR ON |
| | THE ADJACENT FLOOR LEADING TO THE EXIT. |
| | |
| | 1B) FBC-B 1018.1 CONSTRUCTION. CORRIDORS SHALL BE |
| | FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1018.1. |
| | THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED |
| | SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. |
| | 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL |
| | HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | |
| | 1C) FBC-B 708.4 CONTINUITY. FIRE PARTITIONS SHALL |
| | EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING |
| | ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF |
| | SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO. |
| | |
| | 1D) FBC-B 717.5.4 FIRE PARTITIONS. DUCTS AND AIR |
| | TRANSFER OPENINGS THAT PENETRATE FIRE PARTITIONS SHALL |
| | BE PROTECTED WITH LISTED FIRE DAMPERS INSTALLED IN |
| | ACCORDANCE WITH THEIR LISTING. |
| | |
| | 1E) FBC-B 717.4 ACCESS AND IDENTIFICATION. |
| | FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN |
| | APPROVED MEANS OF ACCESS, WHICH IS LARGE ENOUGH TO |
| | PERMIT INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS |
| | OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE |
| | INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE |
| | ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE |
| | RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE |
| | PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL |
| | HAVING LETTERS NOT LESS THAN 1/2 INCH (12.7 MM) IN |
| | HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE |
| | DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING |
| | AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION. |
| | |
| | 1F) FBC-B 703.7 MARKING AND IDENTIFICATION. |
| | FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| | BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS |
| | SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING. SUCH IDENTIFICATION SHALL: |
| | 1F) 1. BE LOCATED IN ACCESSIBLE CONCEALED FLOOR, |
| | FLOOR-CEILING OR ATTIC SPACES; |
| | 1F) 2. BE LOCATED WITHIN 15 FEET (4572 MM ) OF THE END |
| | OF EACH WALL AND AT INTERVALS NOT EXCEEDING 30 FEET |
| | MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION; AND |
| | 1F) 3. INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM |
| | ) IN HEIGHT WITH A MINIMUM 3/8 INCH (9.5 MM) STROKE IN |
| | A CONTRASTING COLOR INCORPORATING THE SUGGESTED |
| | WORDING. ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL |
| | OPENINGS? OR OTHER WORDING. |
| | |
| | 2 COMPLIED. |
| | |
| | 3) 2ND REQUEST, PLANS STILL SHOW A MICROWAVE OUT OF THE |
| | REACH RANGES AND OPERATING PARTS RANGE!!!!!SHEET A.5 |
| | DETAIL 1 SHOWS A MICROWAVE ON THE BOTTOM SHELF OF THE |
| | UPPER CABINETS. PLEASE REVIEW 2014 FBC-ACCESS. CODE |
| | REACH RANGES IN 308 AND OPERABLE PARTS UNDER 309.3 |
| | HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR |
| | MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | |
| | 4)2ND REQUEST, CONTRACTOR HAS NOT SUBMITTED SHEET M2 |
| | INDICATES THE USE OF NEW ROOF TOP A/C STANDS. PLEASE |
| | PROVIDE COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(G) PRE-ENGINEERED A/C STANDS / WALL LOUVERS FOR |
| | OUTSIDE AIR. |
| | |
| | 5-8) COMPLIED. |
| | |
| | 9A) NEW COMMENT OUTSIDE AIR LOUVER A SALES BROCHURE WAS |
| | SUBMITTED NOT A MIAMI DADE NOA. 2014 FBC-B 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS:, WALL LOUVERS, |
| | 9B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | AMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |