| Plan Review Notes For Permit 16070025 |
| Permit Number |
16070025 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-23 11:21:57 | 1) THE SINK IN THE HALL BY THE DRESSING ROOMS SHALL | | | COMPLY WITH FBC-ACCESIBILITY SEC. 212.3. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | RECTORSEAL WATERLESS TRAP.THIS INFORMATION WILL BE | | | REVIEWED FOR COMPLIANCE WITH THE PLUMBING CODE. | | | 3) THE BRANCH VENT FROM SK-1 APPEARS TO BE OVER 40 FEET | | | IN DEVELOPED LENGTH. THE VENT SHALL BE INCREASED TO 3 | | | INCHES FOR THE ENTIRE DEVELOPED LENGTH PER 2014 FBC - | | | PLUMBING SEC.906.2. | | | 4) GRAB BARS SHALL BE MEASUREDD TO THE TOP OF THE | | | GRIPPING SURFACE. FAC SEC.609.4. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|