Plan Review Notes
Plan Review Notes For Permit 16070025
Permit Number 16070025
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-11 09:12:091ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16070025
 7/11/16
  
 1) IN REGARD TO THE SUBMITTED AC CALCULATIONS PREPARED
 FOR THE PROJECT BY TOM PLATANIA- PRO CALCS LLC., PLEASE
 REFER TO SECTION 105.3.1.2(3) FBC-14 BUILDING:
 AN AIR-CONDITIONING SYSTEM MAY BE DESIGNED BY AN
 INSTALLING AIR-CONDITIONING CONTRACTOR CERTIFIED UNDER
 CHAPTER 489, FLORIDA STATUTES, TO SERVE ANY BUILDING OR
 ADDITION WHICH IS DESIGNED TO ACCOMMODATE FEWER THAN
 100 PERSONS AND REQUIRES AN AIR-CONDITIONING SYSTEM
 WITH A VALUE OF $125,000 OR LESS; AND WHEN A 15-TON-PER
 SYSTEM OR LESS IS DESIGNED FOR A SINGULAR SPACE OF A
 BUILDING AND EACH 15-TON SYSTEM OR LESS HAS AN
 INDEPENDENT DUCT SYSTEM. SYSTEMS NOT COMPLYING WITH THE
 ABOVE REQUIRE DESIGN DOCUMENTS THAT ARE TO BE SEALED BY
 A PROFESSIONAL ENGINEER.
 PLEASE CLARIFY IF MR. PLATANIA IS EITHER THE ENGINEER
 OF RECORD OR THE INSTALLING AC CONTRACTOR.
  
 2) INDICATE WHICH AC SYSTEM SHOWN ON THE PLANS IS BEING
 SIZED IN ACCORDANCE WITH THE AC CALCULATIONS.
  
 3) REFER TO PAGE 3 OF THE SUBMITTED ENERGY GAUGE
 CALCULATION SUBMITTAL: THE OWNER/AGENT AND ARCHITECT
 MUST SIGN THE DOCUMENT.
  
 4) PROVIDE A DUPLICATE COPY OF THE ENERGY GAUGE INPUT
 DATA REPORT- ONLY ONE COPY WAS SUBMITTED.
  
 5) IT APPEARS THAT AC SYSTEMS #7 & # 8 ARE NOT LISTED
 IN THE ENERGY CALCULATIONS, AND THE DESIGNER OR
 ENGINEER HAS NOT FILLED OUT THE CHECKLIST ON PAGE 7.
  
 6) DUCT SMOKE DETECTORS SHALL BE PLACED IN THE RETURN
 AIR SYSTEMS OF AC SYSTEMS #5 & #8- SEE SECTION 606.2.1.
  
 7) SHEETS A.1 & M.1: AC-8 HAS BEEN SIZED PER THE HEAT
 LOAD FROM EQUIPMENT. PLEASE IDENTIFY THE EQUIPMENT
 SHOWN IN EQPT 115, AND IF IT IS COMPUTER EQUIPMENT,
 PLEASE PROVIDE THE SCOP RATING OF THE SYSTEM PER TABLE
 C403.2.3 FBC-14 ENERGY CONSERVATION.
  
 8) A.1 & M.1: PLEASE IDENTIFY ALL ROOMS AND SPACES
 SHOWN ON THE HVAC PLAN.
  
 9) M.1: PROVIDE A CONDENSATE DISPOSAL PLAN- SHOW PIPING
 RUNS AND DISCHARGE LOCATIONS, AND INDICATE THE TYPES
 AND SIZES OF PIPINGS.
  
 10) M.1: THE RESTROOM EF-1'S SHALL EACH HAVE MINIMUM 70
 CFM CAPACITY PER TABLE 403.3.
  
 11) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE
 LOCATIONS OF ALL NEW EQUIPMENT AND CLEARANCE DISTRANCES
 TO ROOF EDGES, AIR INTAKES ETC.
  
 12) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR THE AC STAND AND O/A INTAKE LOUVERS WITH
 SHOP DRAWING APPROVAL SIGNATURES OF THE DOCUMENTS BY
 THE DESIGN PROFESSIONAL OF RECORD- FLORIDA DEPT. OF
 COMMUNITY AFFAIRS RULE 9N-3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved