| Date |
Text |
| 2016-07-11 09:12:09 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16070025 |
| | 7/11/16 |
| | |
| | 1) IN REGARD TO THE SUBMITTED AC CALCULATIONS PREPARED |
| | FOR THE PROJECT BY TOM PLATANIA- PRO CALCS LLC., PLEASE |
| | REFER TO SECTION 105.3.1.2(3) FBC-14 BUILDING: |
| | AN AIR-CONDITIONING SYSTEM MAY BE DESIGNED BY AN |
| | INSTALLING AIR-CONDITIONING CONTRACTOR CERTIFIED UNDER |
| | CHAPTER 489, FLORIDA STATUTES, TO SERVE ANY BUILDING OR |
| | ADDITION WHICH IS DESIGNED TO ACCOMMODATE FEWER THAN |
| | 100 PERSONS AND REQUIRES AN AIR-CONDITIONING SYSTEM |
| | WITH A VALUE OF $125,000 OR LESS; AND WHEN A 15-TON-PER |
| | SYSTEM OR LESS IS DESIGNED FOR A SINGULAR SPACE OF A |
| | BUILDING AND EACH 15-TON SYSTEM OR LESS HAS AN |
| | INDEPENDENT DUCT SYSTEM. SYSTEMS NOT COMPLYING WITH THE |
| | ABOVE REQUIRE DESIGN DOCUMENTS THAT ARE TO BE SEALED BY |
| | A PROFESSIONAL ENGINEER. |
| | PLEASE CLARIFY IF MR. PLATANIA IS EITHER THE ENGINEER |
| | OF RECORD OR THE INSTALLING AC CONTRACTOR. |
| | |
| | 2) INDICATE WHICH AC SYSTEM SHOWN ON THE PLANS IS BEING |
| | SIZED IN ACCORDANCE WITH THE AC CALCULATIONS. |
| | |
| | 3) REFER TO PAGE 3 OF THE SUBMITTED ENERGY GAUGE |
| | CALCULATION SUBMITTAL: THE OWNER/AGENT AND ARCHITECT |
| | MUST SIGN THE DOCUMENT. |
| | |
| | 4) PROVIDE A DUPLICATE COPY OF THE ENERGY GAUGE INPUT |
| | DATA REPORT- ONLY ONE COPY WAS SUBMITTED. |
| | |
| | 5) IT APPEARS THAT AC SYSTEMS #7 & # 8 ARE NOT LISTED |
| | IN THE ENERGY CALCULATIONS, AND THE DESIGNER OR |
| | ENGINEER HAS NOT FILLED OUT THE CHECKLIST ON PAGE 7. |
| | |
| | 6) DUCT SMOKE DETECTORS SHALL BE PLACED IN THE RETURN |
| | AIR SYSTEMS OF AC SYSTEMS #5 & #8- SEE SECTION 606.2.1. |
| | |
| | 7) SHEETS A.1 & M.1: AC-8 HAS BEEN SIZED PER THE HEAT |
| | LOAD FROM EQUIPMENT. PLEASE IDENTIFY THE EQUIPMENT |
| | SHOWN IN EQPT 115, AND IF IT IS COMPUTER EQUIPMENT, |
| | PLEASE PROVIDE THE SCOP RATING OF THE SYSTEM PER TABLE |
| | C403.2.3 FBC-14 ENERGY CONSERVATION. |
| | |
| | 8) A.1 & M.1: PLEASE IDENTIFY ALL ROOMS AND SPACES |
| | SHOWN ON THE HVAC PLAN. |
| | |
| | 9) M.1: PROVIDE A CONDENSATE DISPOSAL PLAN- SHOW PIPING |
| | RUNS AND DISCHARGE LOCATIONS, AND INDICATE THE TYPES |
| | AND SIZES OF PIPINGS. |
| | |
| | 10) M.1: THE RESTROOM EF-1'S SHALL EACH HAVE MINIMUM 70 |
| | CFM CAPACITY PER TABLE 403.3. |
| | |
| | 11) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE |
| | LOCATIONS OF ALL NEW EQUIPMENT AND CLEARANCE DISTRANCES |
| | TO ROOF EDGES, AIR INTAKES ETC. |
| | |
| | 12) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT |
| | APPROVALS FOR THE AC STAND AND O/A INTAKE LOUVERS WITH |
| | SHOP DRAWING APPROVAL SIGNATURES OF THE DOCUMENTS BY |
| | THE DESIGN PROFESSIONAL OF RECORD- FLORIDA DEPT. OF |
| | COMMUNITY AFFAIRS RULE 9N-3. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |